TFP1920
Page 2 of 4
Installation
The installation instructions for the
TYCO CPVC Hanger Head Set Model
SHB1 for different types of wood joist
are defined in the following sections:
• Hanger Head Set — Solid Wood
Joist
• Hanger Head Set — Composite
Wood Joist
NOTICE
The TYCO CPVC Hanger Head Set
Model SHB1 does not meet the UL
requirement for providing vertical
restraint that may result from a sprin-
kler activation. A number of hanger
techniques (not inclusive of the use
of a Hanger Head Set) as described
in Installation Handbook IH-1900 can
be used to provide vertical restraint.
Failure to provide vertical restraint may
result in vertical lift upon sprinkler acti-
vation and the inability of a sprinkler to
spray effectively in the event of a fire.
Installing sprinklers into the sprin-
kler adapter fittings prior to solvent
cementing the adapters to the drop is
unacceptable. Failure to allow sprin-
kler fitting joint to cure before install-
ing sprinklers may result in cement in
sprinkler waterway and inability of the
sprinkler to properly operate in the
event of a fire.
The hanger head set should not be
installed other than side-mount or
attached to anything other than the
side of a solid wood framing member
or structural composite wood joist, with
the fasteners provided, without prior
review and approval of the authority
having jurisdiction. Any other method
of installation may not comply with
NFPA or local requirements. If the
installer attaches the Hanger Head Set
to another type of structural member or
orients the Hanger Head Set in a posi-
tion other than side-mount, fasteners
and fastener methods shall comply
with applicable NFPA and local code
requirements.
Hanger Head Set - Solid Wood Joist
Step 1.
Position the hanger head set
against the vertical solid wood joist
surface (side-mount).
Step 2.
Set the depth using the gradu-
ated markings on an offset gauge as
shown in Figure 3.
Step 3.
Secure the hanger head set to
the wooden surface using the two #10
x 1 in. hex head lag screws.
Note: The screws are provided. See
Figure 1.
Step 4.
Cut and install the CPVC sprin-
kler drop making sure the face of the
sprinkler head adapter is flush with the
inside of the head set cup.
Step 5.
Insert the sprinkler inlet pipe
threads through the head set cup and
thread into the CPVC adapters using
the instructions provided in the tech-
nical data sheet for the sprinkler, and
Technical Data Sheet TFP700 for the
“INSTALLER WARNING”.
Hanger Head Set - Composite
Wood Joist
Step 1.
Use a pliers to break off the
breakaway tabs as shown in Figure 4.
Step 2.
Use the pliers to bend the lower
hanger mounting flange to a 90 degree
angle as shown in Figure 4.
Step 3.
Position the hanger head set
against the composite wood joist web
member (side-mount).
Step 4.
Set the depth using the grad-
uated markings of an offset gauge as
shown in Figure 3.
Step 5.
Secure the hanger head set to
the wooden surface using the two #10
x 1 in. hex head lag screws.
Note: The screws are provided. See
Figure 1.
Step 6.
Cut and install the CPVC sprin-
kler drop making sure the face of the
sprinkler head adapter is flush with the
inside of the head set cup.
Step 7.
Insert the sprinkler inlet pipe
threads through the head set cup and
thread into CPVC adapters using the
instructions provided in the techni-
cal data sheet for the sprinkler, and
Technical Data Sheet TFP700 for the
“INSTALLER WARNING”.
3"
(76,2 mm)
1"
(25,4 mm)
3"
(76,2 mm)
2"
(50,8 mm)
2-3/16"
(55,6 mm)
BUILT-IN
OFFSET GAUGE
IN 1/4" (6,3 mm)
INCREMENTS
SCREW
HOLES
BREAK-
AWAY
TABS
4-1/2"
(114,3 mm)
LOCATING
TABS
#10 x 1"
HEX HEAD
LAG SCREW
(2 PROVIDED)
SPRINKLER HEAD
ADAPTER FLUSH WITH
INSIDE OF HEAD SET CUP
HEAD SET
CUP
1
3
2
4
1
2
ON SOLID WOOD JOISTS,
USE SCREW POSITIONS
1 + 2, 1 + 4, or 2 + 3
ON COMPOSITE WOOD JOISTS,
USE SCREW POSITIONS 1 + 2
LOWER
FLANGE
BEND
AREA
FIGURE 1
MODEL SHB1 HANGER HEAD SET
(NOMINAL DIMENSIONS)