MX TECHNOLOGY
�
Tyco 814 Series
Multi-Sensor
Analogue Addressable Detectors
I N F O R M A T I O N S H E E T
5 June 2009
120.415.744 Issue 13
©Tyco Safety Products - Fire Detection - ANZ Region
Page 1 of 2
SPECIFICATIONS
814PH
814CH
814I
814H
814P
(less base)
Photoelectric/Heat CO/Heat
Ionisation
Heat
Photoelectric
Height
43mm
43mm
43mm
43mm
43mm
Diameter
108mm
108mm
108mm
108mm
108mm
Weight
76g
88g
81g
79g
76g
Loop Voltage
20V to 40Vdc addressable loop voltage is provided by the
MX
c.i.e.
Quiescent Current (typical) 275µA
275µA
330µA
250µA
275µA
Alarm Current
2
3mA
3mA
3mA
3mA
3mA
Alarm Current
3
10mA
10mA
10mA
10mA
10mA
Remote Indicator
Tyco E500Mk2 typical for all detectors
Max. Detectors per Loop
4
200/250
200/250
200/250
200/250
200/250
Ambient Temperature
5
–25°C to +70°C
0 to +50°C
–25°C to +70°C –25°C to +70°C –25°C to +70°C
Storage Temperature
–40°C to +80°C
–10°C to +50°C –40°C to +80°C –40°C to +80°C –40°C to +80°C
Relative Humidity
6
95%
15 to 90%
95%
95%
95%
CSIRO ActivFire listed
afp-1424
afp-1425
afp-1426
afp-1427
afp-1699
Standards
AS1603.1-1997
7
AS1603.1-1997
7
AS1603.2-1997
AS1603.1-1997
7
AS1603.2-1997
AS1603.2-1997
AS1603.2-1997
AS1603.14-2001
Part Number
516.800.510
8
516.800.511
8
516.800.512
516.800.513
8
516.800.517
1. Service replacement only when used on heat detector spacing. 2. Remote Indicator not fitted, excluding isolator / sounder / relay base currents.
3. With Remote Indicator fitted, excluding isolator / sounder / relay base currents.
4. Depends on the c.i.e. used; MX4428/
MX1
, 4100MXP. Refer to c.i.e. manuals for design limitations. 5. Types A & B Heat detector, 45°C max.
6. Maximum, non condensing. 7. AS1603.1-1997 compliance: 814H complies as Types A, B, C, D; 814CH and 814PH comply as Type A & B only.
8. The 814PH, CH, H detectors’ heat sensors are coated to provide extra moisture protection, identified by ‘MP5’ on the label.
DESCRIPTION
•
814PH Photoelectric/Heat
•
814H Heat only
•
814CH Carbon Monoxide/Heat
•
814I Ionisation
•
814P Photoelectric Smoke Only
The 814 Series
MX
Virtual Multi-Sensor detectors transmit
to the Tyco
MX
Control and Indicating Equipment (c.i.e.)
digital values that represent the level of smoke/CO/heat
at the sensors. The c.i.e. software interprets the returned
values, responding (e.g. to raise an alarm) according to the
detection mode configured in the software. By utilising dual
sensors (Photoelectric Smoke & Heat or CO & Heat) the
c.i.e. detection algorithms can achieve optimum detection
by combining the two components in different ways. Heat-
enhanced smoke/CO detection lowers the alarm threshold
when a heat rate-of-rise is detected. A choice of detection
algorithm is available - fuzzy-logic based
MX FASTLOGIC™
or the field-proven
SMARTSENSE™
algorithm. The 814H,
814I and 814P are all single sensor devices. The multi-sensor
detectors can be configured to operate in one of the following
modes:
•
Heat Enhanced Smoke/CO plus heat detection
•
Smoke/CO plus heat detection
•
Heat Enhanced Smoke/CO detection only
•
Smoke/CO detection only
•
Heat detection rate-of-rise & fixed temperature
1
•
Heat detection fixed temperature only
1
All 814 series detectors will plug into the following bases:
•
5B Universal Base
•
M614 Universal Base
•
5BI Isolator Base
•
814IB Isolator Base
•
814RB Relay Base
•
814SB Sounder Base
•
802SB Sounder Base
•
901SB Sounder Base
Note: For 814P applications, MXP firmware must be at least V1.13 and 801AP firmware at least V2.2.