Tyco Issue A Manual Download Page 3

Care and
Maintenance

The Issue A and B Window Type Ex-
posure Protection Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:

NOTE

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.

Issue A and B Window Type Exposure
Protection Sprinklers must never be
painted, plated, coated or altered in
any way after leaving the factory; oth-
erwise, the spray performance may be
impaired.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinkler dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.

Frequent visual inspections are rec-
ommended to be initially performed for
nozzles installed in potentially corro-
sive atmospheres to verify the integrity
of the materials of construction as they
may be affected by the corrosive con-
ditions present for a given installation.
Thereafter, annual inspections per
NFPA 25 are required.

Exposure protection systems for the
outside of buildings require regularly
scheduled care and maintenance by
trained personnel. In addition to in-
specting sprinklers for proper spray
performance during water flow trip
tests of the system, it is recommended
that sprinklers be periodically in-
spected for loading/obstructions, or
other evidence of impaired protection.
The inspections should be scheduled
weekly or as frequently as may be
necessary, and corrective action must
be taken to ensure that the sprinkler
will perform as intended in the event of
a fire.

The owner is responsible for the in-
spection, testing, and maintenance of
their exposure protection system and
devices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-

TFP835

Page 3 of 4

FIGURE 2

ISSUE A WINDOW TYPE EXPOSURE PROTECTION SPRINKLERS

NOMINAL DISCHARGE PATTERNS

Provided for reference only. Refer to NFPA 13 for the required distance to

window as a function of window width.

EACH SQUARE

= 1 SQ. FT.

WEL DEFINED

OUTLINE

(180 mm)

5/16" & 3/8"

ORIFICE

SPRINKLER

1/4"

ELEVATION

ORIFICE

1/4" & 5/16"

ORIFICE

PLAN

1/2"

LITTLE

FINE SPRAY

ORIFICE

SURFACE

GLAZING

SHOWN AT

7"

FLOWING

PRESSURE

(2,1 BAR)

30 PSI

FIGURE 3

ISSUE B WINDOW TYPE EXPOSURE PROTECTION SPRINKLERS

NOMINAL DISCHARGE PATTERNS

Provided for reference only. Refer to NFPA 13 for the required distance

to window as a function of window width.

SHOWN AT

(2,1 BAR)

PRESSURE

FLOWING

ORIFICE

1/2"

5/8"

3/4"

ORIFICE

ORIFICE

WEL DEFINED

SPRINKLER

ELEVATION

OUTLINE

GLAZING

SURFACE

ORIFICE

1/2"

5/8"

3/4"

ORIFICE

ORIFICE

30 PSI

EACH SQUARE

FINE SPRAY

PLAN

LITTLE

(215 mm)

8-1/2"

= 1 SQ. FT.

Reviews: