Tyco BFV-N Manual Download Page 3

TFP1510

Page 3 of 4

Installation

The Model BFV-N Grooved End Butter-

fly Valves may be installed with flow in 

either direction and can be positioned 

either horizontally or vertically.
The grooved end pipe couplings used 

with the Model BFV-N must be listed or 

approved for fire protection service and 

installed in accordance with the manu-

facturers instructions.
The Model BFV-N Butterfly Valve may 

be installed with any schedule of pres-

sure class of pipe or tubing that is listed 

or approved for fire protection.
As applicable, refer to Figure 2 for the 

internal switch wiring diagram.
Conduit and electrical connections 

are to be made in accordance with 

the authority having jurisdiction and/

or the National Electrical Code. With 

reference to Figure 2, the supervisory 

switch is intended for connection to 

the supervisory circuit of a fire alarm 

control panel in accordance with NFPA 

72. The auxiliary switch is intended for 

the unsupervised connection to aux-

iliary equipment in accordance with 

NFPA 70, National Electric Code.

NOTE:

 For outdoor applications with 

internal supervisory switches, it is rec-

ommended that wiring connections 

be made at a temperature above 15°F  

(-9°C), in order to insure sufficient flex-

ibility of the wire lead insulation.

Stop 

Adjustment 

Procedure

The gear operator’s OPEN and SHUT 

position have been factory set. The 

following procedure should be used if 

slight adjustments are needed. Refer to 

Figure 3.

Step 1.

 Turn the Handwheel until the 

valve is fully closed.

Step 2.

 Remove two lockscrews (A) 

from the gear operator body.

Step 3.

 Turn the Shut Stop Screw (B) 

clockwise until snug.

Step 4.

 Turn the Handwheel until the 

valve is fully open.

Step 5.

 Turn the Open Stop Screw (C) 

clockwise until snug.

Step 6.

 Close the valve by turning the 

Handwheel until the valve is fully in 

the closed position. Ensure the disc 

has returned to the fully closed posi-

tion and the disc is centered in the seat 

area. Readjust the Shut Stop Screw if 

necessary.

Step 7.

 Replace two lockscrews (A) 

into the gear Operator body locking 

the stops into position.

10 INCH (DN250)

8 INCH (DN200)

6 INCH (DN150)

5 INCH (DN125)

4 INCH (DN100)

3 INCH (DN80)

2-1/2 INCH (DN65)

2.0

0.4

0.1

0.2

0.3

0.6
0.5

0.8

1.0

3.0

4.0

5.0

60

100

200

600

400

1000

2000

10000

6000

4000

600

10000

6000

1000

2000

4000

20000

40000

400

0,30

0,20

0,08

0,10

0,06

0,04

0,05

0,03

0,02

0,01

FLOW RATE IN LITRES PER MINUTE (LPM)

FLOW RATE IN GALLONS PER MINUTE (GPM)

NOMINAL PRESSURE DROP

IN POUNDS PER SQUARE INCH (PSI)

(1 PSI = 0,06895 BAR)

NOMINAL PRESSURE DROP IN BAR

(1 GPM = 3,785 LPM)

15000

300

A

C

A

B

OPEN

SHUT

GRAPH A 

DN65 THROUGH DN250 MODEL BFV-N BUTTERFLY VALVE 

NOMINAL PRESSURE DROP VERSUS FLOW

FIGURE 3 

MODEL BFV-N GROOVED END 

BUTTERFLY VALVE 

OPERATOR ADJUSTMENT