TFP443

Page 4 of 6

Maximum  

Coverage  

Area 

(a)

Ft. x Ft.  

(m x m)

Maximum 

Spacing

Ft.  

(m)

WET PIPE SYSTEM

Minimum Flow and Residual Pressure

(b, c)

Ordinary Temp Rating 

160°F (71°C)

Deflector to 

Ceiling

Installation 

Type

Minimum 

Spacing 

Ft. 

(m)

Flow 

GPM 

(L/min)

Pressure 

PSI 

(bar)

12 x 12

(3,7 x 3,7)

12

(3,7)

13 

(49,2)

7.0 

(0,48)

Smooth 

Ceilings 7/8 to 

1-1/8 inches.

Beamed 

Ceilings per 

NFPA 13D  

 13R, or 13  

Installed in 

beam 7/8 to 

1-1/8 inches 

below bottom 

of beam

Concealed

(2,4)

14 x 14

(4,3 x 4,3)

14

(4,3)

13 

49,2)

7.0 

(0,48)

16 x 16

(4,9 x 4,9)

16

(4,9)

13

(49,2)

7.0 

(0,48)

18 x 18

(5,5 x 5,5)

18

(5,5)

17 

(64,3)

12.0 

(0,83)

20 x 20

(6,1 x 6,1)

20

(6,1)

20 

(75,7)

16.7 

(1,15)

(a)   For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest 

coverage area for which Hydraulic Design section under the Design Criteria are stated.

(b)   The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pres-

sures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.

(c)   For NFPA 13 residential applications, the greater of 0.1 gpm/ft.

2

 over the design area or the flow in accordance with the 

criteria in this table must be used.

Maximum  

Coverage  

Area 

(a)

Ft. x Ft.  

(m x m)

Maximum 

Spacing

Ft.  

(m)

DRY PIPE SYSTEM

Minimum Flow

 

and Residual Pressure

(b)

Ordinary Temp Rating 

160°F (71°C)

Deflector to 

Ceiling

Installation 

Type

Minimum 

Spacing 

Ft. 

(m)

Flow 

GPM 

(L/min)

Pressure 

PSI 

(bar)

12 x 12

(3,7 x 3,7)

12

(3,7)

15 

(56,8)

9.4 

(0,65)

Smooth 

Ceilings 7/8 to 

1-1/8 inches.

Beamed 

Ceilings per 

NFPA 13D  

 13R, or 13  

Installed in 

beam 7/8 to 

1-1/8 inches 

below bottom 

of beam

Concealed

(2,4)

14 x 14

(4,3 x 4,3)

14

(4,3)

15 

(56,8)

9.4 

(0,65)

16 x 16

(4,9 x 4,9)

16

(4,9)

16 

(60,6)

10,7 

(0,74)

18 x 18

(5,5 x 5,5)

18

(5,5)

17 

(64,3)

12.0 

(0,83)

20 x 20

(6,1 x 6,1)

20

(6,1)

21 

(79,5)

18,4 

(1,27)

(a)   For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest  

coverage area for which Hydraulic Design section under the Design Criteria are stated.

(b)   The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual 

pressures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.

(c)   For NFPA 13 residential applications, the greater of 0.1 gpm/ft.

2

 over the design area or the flow in accordance with the 

criteria in this table must be used.

TABLE A 

WET PIPE SYSTEM 

SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) 

NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

TABLE B 

DRY PIPE SYSTEM 

SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) 

NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA