Introduction

The Color Touchscreen LCD Annunciator for the

 

AUTOPULSE Z-20 Agent Releasing Panel* 

provides remote annunciation of the AUTOPULSE Z-20. Visual status is provided by the 
touchscreen and by the LEDs. Audible annunciation is provided through a piezo sounder. Access 

to the annunciator switch functions can be enabled or locked using the keyswitch. A maximum of 

six color touchscreen annunciators can be installed on an AUTOPULSE Z-20 panel.

*AUTOPULSE Z-20 Agent Releasing Panel, from this point on, will be referred to as the 

AUOPULSE Z-20.

Compatibility

The AUTOPULSE Z-20 must be at revision 3.02.07 or higher to support the Color Touchscreen 
LCD Annunciator.
The following annunciators, boxes, and brackets are compatible with the

 

AUTOPULSE Z-20:

Reference 
Documents

Refer to the following documents for more information on how to program and

 

use the remote 

annunciator.

In this 
publication

Introduction ................................................. 3 Compatibility ............................................... 3
Reference Documents  
................................ Wire Length Tables  ..................................... 7
Module Overview  ........................................ Communication Wiring Length Tables  ........ 8
General Mounting Information  .................... Address Setting ........................................... 8
General Wiring Guidelines .......................... Mounting Instructions ................................ 10
Specific Wiring Guidelines  .......................... Verification Procedure ............................... 10
Wiring .......................................................... Remote Annunciator Specifications  .......... 11

Part Number

Description

4606-9202AR

AUTOPULSE

 

Color Touchscreen LCD Annunciator, Red

2975-9461

AUTOPULSE

 

Color Touchscreen LCD Annunciator, Surface Mount Box, 

Red

2975-9463

AUTOPULSE Color Touchscreen LCD Annunciator, Retrofit, Semi-flush 
bracket, Red

Document Number

Title

579-1165AR

AUTOPULSE Z-20 Operator’s manual

579-1167AR

AUTOPULSE Z-20 Programmer’s manual

Color Touchscreen LCD Annunciator Installation Instructions

Summary of Contents for AutoPulse Z-20

Page 1: ...Z 20 COLOR TOUCHSCREEN LCD ANNUNCIATOR Copyright 2016 Tyco Fire Protection Products LP All rights reserved www tyco com 579 1172AR Rev A INSTALLATION MANUAL...

Page 2: ...nd notify an authorized AUTOPULSE product supplier ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs All repairs should be performed by a representati...

Page 3: ...ble with the AUTOPULSE Z 20 Reference Documents Refer to the following documents for more information on how to program and use the remote annunciator In this publication Introduction 3 Compatibility...

Page 4: ...h SW 2 Sets AUTOPULSE Z 20 address and communications online or offline Reset Switch SW1 Short press 5 seconds to activate a software reset warm start Press and hold 5 seconds to force a hardware rese...

Page 5: ...and power limited The Remote Annunciator cannot be used with wiring that goes outside the building above or below ground unless overvoltage suppression is provided at both ends for both the communica...

Page 6: ...OMM and Power Line TB1 1 24V IN from AUTOPULSE Z 20 Power Supply or Previous Annunciator TB1 2 24V OUT to Next Annunciator TB1 3 24C IN from AUTOPULSE Z 20 Power Supply or Previous Annunciator TB1 4 2...

Page 7: ...G 3 309 mm 14 AWG 2 801 mm 16 AWG 1 309 mm 18 AWG 0 823 mm 0 100 2 500 ft 762 m 2 500 ft 762 m 2 500 ft 762 m 2 349 ft 715 97 m 0 200 2 500 ft 762 m 2 500 ft 762 m 1 482 ft 451 71 m 1 175 ft 358 14 m...

Page 8: ...card address for the AUTOPULSE Z 20 Refer to Table 6 for a complete list of the switch settings for all of the possible card addresses Set each card to the address assigned in the AUTOPULSE Programme...

Page 9: ...ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF 32 ON OFF ON ON ON ON ON 9...

Page 10: ...verify that the remote annunciator is working properly If the annunciator displays the message Error communicating with Master or if the annunciator fails to power check the wiring If the wiring is co...

Page 11: ...perating Humidity Range Up to 93 relative humidity at 100o F 38o C non condensing Power Supply 24 V DC Nominal 18 V DC minimum at power input terminals of annunciator to allow for wiring losses Maximu...

Page 12: ...579 1172AR Rev A...

Reviews: