INSTALLATION
The 5.6 K-Factor, SuperNova S120 Sprinklers must be in-
stalled in accordance with the following instructions:
NOTES
A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 14,0 Nm). A
maximum of 21 ft.lbs. (28,5 Nm) of torque is to be used to
install sprinklers. Higher levels of torque may distort the
sprinkler inlet with consequent leakage or impairment of
the sprinkler.
Do not attempt to compensate for insufficient adjustment
in an Escutcheon Plate by under- or over-tightening the
Sprinkler. Readjust the position of the sprinkler fitting to
suit.
1. Upright sprinklers must be installed only in the upright
position and pendent sprinklers must be installed only in
the pendent position. The deflector is to be parallel to
the ceiling, roof, or mounting surface, as applicable.
2. After installing the #2084 mounting plate (or other es-
cutcheon, as applicable) over the sprinkler pipe threads
and with pipe thread sealant applied to the pipe threads,
hand tighten the sprinkler into the sprinkler fitting.
3. Wrench tighten the Sprinkler using only the W-Type 11
or W-Type 12 Sprinkler Wrench (Ref. Figure 3). The
wrench recess of the W-Type 11 or W-Type 12 is to be
applied to the sprinkler wrenching area (Ref. Figure 1).
The W-Type 12 is to be used when the sprinkler
wrench area is inaccessible as in the case of a fixed ceil-
ing, recessed installation.
STAR SPRINKLER
Page 2
1-1.2.82
FIGURE 1
5.6 K-FACTOR, SUPERNOVA S120
PENDENT AND UPRIGHT SPRINKLERS
FIGURE 2
5.6 K-FACTOR, SUPERNOVA PENDENT SPRINKLER
WITH #2084 RECESSED ESCUTCHEON
SPRINKLER FINISH
Temperature
Rating
Frame
Color Code
Natural
Brass
Chrome
Plated
Natural
Brass
140°F/60°C
165°F/74°C
212°F/100°C
Plain
White
Plain
Upright
(S1864)
Recessed (S1865)
With #2084 Escutcheon
N/A
1, 2, 5
Notes:
1. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers.
2. Listed by Underwriters’ Laboratories of Canada as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation as Quick Response Sprinklers for use in Light and Ordinary
Hazard (Groups 1 and 2) Occupancies. (FM limits quick response sprinklers to wet pipe sprinkler systems and
preaction systems qualifying as wet pipe sprinkler systems.)
4. Approved by the Loss Prevention Council (United Kingdom) as Quick Response Sprinklers.
5. Accepted by the City of New York under MEA 188-99-E.
N/A: Not Available.