STAR SPRINKLER
1-2.2.30
Page 3
TABLE B
UL AND C-UL LISTING CRITERIA FOR INSTALLATION OF
8.0 K-FACTOR SG S180 EXTENDED COVERAGE LIGHT HAZARD
PENDENT AND RECESSED PENDENT SPRINKLERS
RESPONSE
COVERAGE AREA
W x L
FT. x FT. (m x m)
MINIMUM
FLOW
(b)
GPM (LPM)
MINIMUM
PRES.
(b)
PSI (BAR)
PENDENT
SPRINKLER
TEMP. RATING
°F
16 x 16 (4,9 x 4,9)
135, 155, 175
26 (98)
10.6 (0,73)
40 (151)
25.0 (1,72)
QUICK
135, 155, 175
18 x 18 (5,5 x 5,5)
20 x 20 (6,1 x 6,1)
16.0 (1,10)
32 (121)
135, 175
NOTES:
(a) The SG S180 (S2420) Sprinklers may be used in QR-EC and EC, as applicable, Light Hazard Occupancy automatic sprinkler applications
per NFPA 13.
(b) Requirement is based on minimum flow in GPM from each sprinkler. The indicated residual pressures are based on the nominal K-factor.
(c) The SG S180 (S2420) Sprinklers are only permitted to be used with unobstructed, smooth ceiling construction as defined by NFPA 13.
(d) Follow the requirements of NFPA 13 for spacing of the SG S180 (S2420) Sprinklers with respect to ceiling mounted obstructions.
(e) The minimum allowable spacing between the SG S180 (S2420) Sprinklers, to prevent cold soldering, is 8 feet (2,4 m).
(f) The maximum permitted ceiling slope for SG S180 (S2420) Sprinklers is a 2 inch (50,8 mm) rise over a 12 inch (304,8 mm) horizontal
run.
(g) The deflector-to-ceiling distance for the SG S180 (S2420) Sprinklers is 1-5/8 to 12 inches (41,3 to 304,8 mm), unless the #2086 Recessed
RECESSED
SPRINKLER
TEMP. RATING
°F
135, 155, 175
135, 155, 175
135, 175
STANDARD
16 x 16 (4,9 x 4.9)
18 x 18 (5,5 x 5,5)
20 x 20 (6,1 x 6,1)
26 (98)
32 (121)
40 (151)
10.6 (0,73)
16.0 (1,10)
25.0 (1,72)
200
200
155, 200
200
200
155, 200
TABLE C
FM APPROVAL CRITERIA FOR INSTALLATION OF
8.0 K-FACTOR SG S180 EXTENDED COVERAGE LIGHT HAZARD
PENDENT AND RECESSED PENDENT SPRINKLERS
RESPONSE
COVERAGE AREA
W x L
FT. x FT. (m x m)
MINIMUM
FLOW
(b)
GPM (LPM)
MINIMUM
PRES.
(b)
PSI (BAR)
PENDENT
SPRINKLER
TEMP. RATING
°F
16 x 16 (4,9 x 4,9)
135, 155, 175
26 (98)
10.6 (0,73)
40 (151)
25.0 (1,72)
QUICK
135, 155, 175
18 x 18 (5,5 x 5,5)
20 x 20 (6,1 x 6,1)
16.0 (1,10)
32 (121)
135, 155, 175
NOTES:
(a) The SG S180 (S2420) Sprinklers may be used in QR-EC and EC, as applicable, Light Hazard Occupancy automatic sprinkler system
applications per FM installation standards.
(b) Requirement is based on maintaining both minimum flow and minimum pressure.
(c) The SG S180 (S2420) Sprinklers are only permitted to be used with smooth level ceilings per FM installation standards.
(d) The minimum allowable spacing between the SG S180 (S2420) Sprinklers, to prevent cold soldering, is 8 feet (2,4 m).
(e) The maximum permitted ceiling slope for SG S180 (S2420) Sprinklers is a 1 inch (25,4 mm) rise over a 12 inch (304,8 mm) horizontal
run.
(f) The deflector-to-ceiling distance for the SG S180 (S2420) Sprinklers is 1-5/8 to 4 inches (41,3 to 101,6 mm), unless the #2086 Recessed
Escutcheon is utilized.
RECESSED
SPRINKLER
TEMP. RATING
°F
135,
135
135
STANDARD
16 x 16 (4,9 x 4,9)
18 x 18 (5,5 x 5,5)
20 x 20 (6,1 x 6,1)
26 (98)
32 (121)
40 (151)
10.6 (0,73)
16.0 (1,10)
25.0 (1,72)
-
-
-
155, 175
155, 175
155, 175
OBSOLETE