STAR SPRINKLER

1-4.1.21

Page 3

TYPE

TEMPERATURE

BULB

LIQUID

COLOR

NATURAL

BRASS

SPRINKLER FINISH

NOTES:

1. Listed by Underwriters Laboratories, Inc. (UL Listed) for Applications A, B, and D.

2. Listed by Underwriters Laboratories, Inc. (UL Listed) for Applications A, C, and D.

3. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed) for Application A, B, and D.

4. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed) for Application A, C, and D.

APPLICATION A:
Installed in accordance with NFPA 13 standard sprinkler position and area/density flow calculation requirements for light, ordinary,
or extra hazard occupancies with a minimum residual (flowing) pressure of 7 psi (0,5 bar).

APPLICATION B:
Installed in accordance with NFPA 13 standard sprinkler position and area/density flow calculation requirements for high piled stor-
age occupancies with a minimum residual (flowing) pressure of 7 psi (0,5 bar).

APPLICATION C:
Installed in accordance with NFPA 13 standard sprinkler position and area/density flow calculation requirements for high piled stor-
age occupancies with a minimum residual (flowing) pressure of 10 psi (0,7 bar).

APPLICATION D (“Specific Application” with ceiling only protection, i.e., no in-rack sprinklers):
When acceptable to the Authority Having Jurisdiction, installed to protect single, double, multiple-row, or portable rack storage (no
solid shelves), as well as palletized or solid piled storage, of Class I-IV commodity, encapsulated or non-encapsulated, as well as
cartoned or uncartoned unexpanded Group A or B plastics, or, cartoned expanded Group A or B plastics, with:

a storage height of up to 20 feet (6,1m);
a maximum ceiling height of 25 feet (7,6m);
a minimum deflector to top of storage clearance of 36 inches (0,9m);
a minimum design density of 0.60 gpm/ft

2

(24 mm/min);

a minimum residual (flowing) pressure of 10 psi (0,7 bar);
a minimum “Reduced Design Area” of 2000 ft

2

(186 m

2

) for wet systems or 2600 ft

2

(242 m

2

) for dry systems;

a maximum coverage area of 100 ft

2

(9,3 m

2

);

NFPA spacing criteria for standard spray sprinklers, i.e. 12 feet (3,7 m)* maximum and 6 feet (1,8 m) minimum;
NFPA deflector-to-ceiling distances; and,
NFPA obstruction criteria for standard spray sprinklers.
*12’-6" (3,8 m) is allowed in 25’-0" (7,6 m) wide bays.

5. Approved by Factory Mutual Research Corporation as follows:

Installed in accordance with the applicable “control mode specific area/density” guidelines provided by Factory Mutual. (FM guide-
lines may differ from UL, C-UL, and ULC Listing criteria.)

(a). UL Listed as corrosion resistant.

(b). FM Approved for a maximum ceiling temperature of 150°F/66°C.

TABLE A

LABORATORY LISTINGS AND APPROVALS

FOR

11.2 K-FACTOR MODEL S160QR PENDENT (SIN S2551) AND UPRIGHT (SIN S2550) SPRINKLERS

UPRIGHT

(S2550)

155°F/68°C

Orange

200°F/93°C

Green

286°F/141°C

Blue

1, 3, 5

135°F/57°C

175°F/79°C

Red

Yellow

PENDENT

(S2551)

2, 4, 5

155°F/68°C

Red

200°F/93°C

Green

286°F/141°C

Blue

CHROME

PLATED

WHITE

POLYESTER

WAX

COATED

LEAD

COATED

WAX

OVER LEAD

COATED

N/A

2

(a)

5

5

(b)

OBSOLETE