1/2 to 12-1/2 inches (114,3 to 317,5 mm) below the ceil-
ing (Ref. Figure 2).

Only the Institutional Escutcheons shown in Figure 3 can
be utilized with the Model PH-5.

NOTES

The Sprinkler Body must not extend beyond the Institu-
tional Escutcheon (Ref. Figure 5). Otherwise the tamper
resistant design of the Model PH-5 will be compromised.

Consequently, #1752 Spacers, which are associated
with other Star institutional sprinklers, cannot to be
utilized.

Integrity of the tamper resistant design of the Institutional
Escutcheon is dependent on the piping installation de-
sign. When installed properly, the Institutional Escutch-
eon is held fast to the mounting surface by the tightening
of the sprinkler assembly into the sprinkler fitting. In order
to accomplish a proper installation, the sprinkler fitting
must be properly located with respect to distance from
the face of the sprinkler fitting to the face of the mounting
surface (Ref. Figure 3); the sprinkler fitting being rigidly
secured and held immobile; and, the centerline of the
sprinkler fitting being perpendicular to the mounting sur-
face to assure that the escutcheon sits squarely against
the mounting surface around the entire perimeter of the
Institutional Escutcheon. Figure 2 illustrates a typical in-
stallation that can be utilized to help adjust the location
of the sprinkler fitting; to help assure immobility of the
sprinkler fitting; and, to help maintain perpendicularity of
the sprinkler fitting to the mounting surface.

STAR SPRINKLER

Page 2

1-5.3.10

FIGURE 1

5.6 K-FACTOR, MODEL PH-5 STANDARD RESPONSE

INSTITUTIONAL HORIZONTAL SIDEWALL SPRINKLER

(71.4 mm)

2.81"

7/16" (11.1 mm)

NOMINAL MAKE-IN

(80.8 mm)

3.18"

SPRINKLER

FACE OF

NPT

FITTING

1/2"

NOTCH (2)

OF SPRINKLER

WATERWAY

CENTERLINE

IN OPERATED

DEFLECTOR

POSITION

(12.7 mm)

1/2"

INSTALL SPRINKLER

SPRINKLER

WRENCHING

TOP AS SHOWN

HAT ORIENTED AT

WITH DEFLECTOR

FIGURE 2

TYPICAL INSTALLATION WITH #1780 RETAINING FLANGE AND #1781 CENTERING GROMMET

REDUCING COUPLING

1" x 1/2" M.I. CLASS 150

5/8" (15.9 mm)

w/ GROOVED

1" STEEL PIPE

WALL THICKNESS

RESULTS IN DEFLECTOR-

4" (101.6 mm) TO 12" (304.8 mm)

TO-CEILING DISTANCE OF

4-1/2" (114.3 mm) TO

12-1/2" (317.5 mm)

*

w/ ESCUTCHEON

MODEL PH-5

WATERWAY

OF SPRINKLER

CENTERLINE

FINISHED

CEILING

*

w/ SET SCREWS

RETAINING

FLANGE

GROMMET

#1781 CENTERING

#1780

2" SCH. 40

(LENGTH TO SUIT

STEEL PIPE SLEEVE

WALL THICKNESS)

OR 2" (50 mm) I.D.

CORED HOLE

END

OBSOLETE