NOTE

Do not install the Luminous S170 into any other type fit-
ting without first consulting the Technical Services Depart-
ment. Failure to use the appropriate fitting may result in:
failure of the sprinkler to properly operate due to binding
of the inlet Plug; or, insufficient engagement of the inlet
pipe threads with consequent leakage.

When Dry Sprinklers are to be used in wet pipe sprinkler
systems protecting areas subject to freezing tempera-
tures (e.g., coolers or freezers), consideration must be
given to the appropriate length of the sprinkler that will
prevent freezing of the water in the connecting pipes, due
to conduction. When the temperature surrounding the wet
pipe sprinkler system is maintained at a minimum tem-
perature of 40°F/4°C, the following are the minimum rec-
ommended lengths between the face of the sprinkler fit-
ting and the outside surface of the protected area (i.e.,
length exposed to minimum ambient of 40°F/4°C):

12 inches (300 mm) when the temperature within the
protected area is -20°F/-29°C

18 inches (450 mm) when the temperature within the
protected area is -40°F/-40°C

24 inches (600 mm) when the temperature within the
protected area is -60°F/-51°C

For protected area temperatures between those given
above, the minimum recommended length from the face
of the fitting to the outside of the protected area may be
determined by interpolating between the indicated values.

NOTE

When Dry Sprinklers penetrate a wall into an area subject
to freezing, the clearance space around the Sprinkler
Casing must be completely sealed in order to prevent the
leakage of moist air into the freezing area which might re-
sult in the formation of condensate around the Frame, De-
flector, Bulb Seat, or Bulb. Failure to prevent the forma-
tion of condensate could result in the build-up of ice
around the releasing components and, consequently,
either an inadvertent operation of the sprinkler or im-
paired operation due to reduced thermal sensitivity.

STAR SPRINKLER

Page 2

1-6.3.11

SPRINKLER FITTING

(REFER TO DESIGN

1" NPT (ISO 7/1 ON SPECIAL REQUEST)

SURFACE

MOUNTING

4" ± 1/8"

(101.6 ± 3.2 mm)

2-1/2" (63.5 mm) MINIMUM

"A" ORDER LENGTH

48" (1.22 m) MAXIMUM

(44.5 mm)

1-3/4" DIA.

FLAT

WRENCH

(WALL)

CRITERIA SECTION)

(76.2 mm)

3" DIA.

3.5°

5/16"

(7.9 mm)

CENTERLINE

OF WATERWAY

SPRINKLER

FITTING

FACE OF

IN 1/4" INCREMENTS

FIGURE 1

LUMINOUS S176 SR DRY HORIZONTAL SIDEWALL SPRINKLER

SPRINKLER FINISH

Temperature

Rating

Bulb

Color Code

Natural

Brass

Chrome

Plated

135°F/57°C

155°F/68°C

175°F/79°C

Red

Yellow

Orange

SIN S3234

“A” Order Length:

2-1/2 to 48 inches

(63,5 to 1219,2 mm)

Deflector-to-Ceiling

Distance:

4 to 12 inches

(100 to 300 mm)

See Note 5

1, 2, 3. 4

Notes:

1. Listed by Underwriters Laboratories, Inc. for use in Light or

Ordinary Hazards.

2. Listed by Underwriters’ Laboratories of Canada for use in

Light or Ordinary Hazards.

3. Approved by Factory Mutual Research Corporation for use in

Light or Ordinary Hazards.

4. Approved by the City of New York under MEA 212-98-E.
5. To meet the requirement of a deflector-to-ceiling distance of

4 to 12 inches, the centerline of the sprinkler waterway

shown in Figure 1 must be 4-5/16 to 12-5/16 inches below
the ceiling.

TABLE A

LUMINOUS S176 STANDARD RESPONSE (SR)

DRY HORIZONTAL SIDEWALL SPRINKLER

LABORATORY LISTINGS AND APPROVALS

1, 2, 3, 4

1, 2, 3, 4

200°F/93°C

286°F/141°C

Green

Blue

1, 2, 3, 4

1, 2, 3, 4

360°F/182°C

Mauve

1, 2, 4

Polyester

(All

Colors)

1, 2, 4

1, 2, 4

1, 2, 4

1, 2, 4

1, 2, 4

1, 2, 4

OBSOLETE