CARE AND MAINTENANCE

The 5.6 and 8.0 K-Factor, Model I-LD-2 Sprinklers must
be maintained and serviced in accordance with the follow-
ing instructions:

NOTE

Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.

Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.

Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over-heated
sprinklers must be replaced.

Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced.

The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.

It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.

LIMITED WARRANTY

Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.

THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.

ORDERING PROCEDURE

Please Specify:

5.6 K-Factor, Model I-LD-2
Upright Intermediate Level Sprinkler (#1809)

5.6 K-Factor, Model LD-2 Pendent Sprinkler (#1801) plus
one 1/2" NPT I-LD-2 Pendent Shield (#1568-02/05) and
two O-rings (#1426)

8.0 K-Factor, Model I-LD-2
Upright Intermediate Level Sprinkler (#1822)

8.0 K-Factor, Model LD-2 Pendent Sprinkler (#1811) plus
one 3/4" NPT I-LD-2 Pendent Shield (#1568-03/06) and
two O-rings (#1426)

W-Type 9 Sprinkler Wrench (#1849)

Refer to Price List for for complete listing of Part Num-
bers with respect to temperature ratings, sprinkler fin-
ishes, etc.

STAR SPRINKLER

Page 4

1-4.2.20

7071 S. 13th Street • Suite 103

Oak Creek, WI 53154

www.starsprinkler.com

PRINTED IN U.S.A. 3-01

OBSOLETE

Summary of Contents for Star I-LD-2

Page 1: ...y two stainless steel balls holds a fusible alloy When the rated temperature is reached the alloy melts the balls are forced toward each other releas ing the tension mechanism which then allows the sprin kler to activate and flow water TECHNICAL DATA Approvals UL and ULC Listed FM and NYC Approved Refer to Table A The approvals apply only to the service conditions indicated in the Design Criteria ...

Page 2: ...EDIATE LEVEL SPRINKLERS NPT 1 2 2 5 8 66 7 mm MAKE IN NOMINAL 11 1 mm 7 16 68 3 mm 2 11 16 PENDENT UPRIGHT WRENCHING AREA 3 76 2 mm DIA SHIELD O RINGS FIELD ASSEMBLED SEE INSTALLATION SECTION FACTORY ASSEMBLED WRENCHING FLANGES MAKE IN NOMINAL 11 1 mm 7 16 1 2 NPT FIGURE 2 8 0 K FACTOR MODEL I LD 2 UPRIGHT AND PENDENT INTERMEDIATE LEVEL SPRINKLERS NPT 3 4 2 11 16 68 3 mm PENDENT UPRIGHT WRENCHING ...

Page 3: ...inkler wrenching area shown in Figure 1 or 2 as applicable Pendent Sprinklers The Model I LD 2 Intermediate Level Pendent Sprinklers must be installed in accordance with the following instruc tions 1 Roll one of the two required O Rings over the sprinkler threads until it seats against the sprinkler wrenching area flange as shown in Figure 1 or 2 as applicable 2 Install the Shield over the sprinkl...

Page 4: ...ed by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordance with applicable Standards of the Na tional Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found b...

Reviews: