Operational Sensitivity Criteria.

For

proper operational sensitivity, the
F978 Sprinklers must be installed be-
neath solid ceilings having a smooth
flat or textured surface and in accord-
ance with Figure A.

The F978 Sprinklers must

NOT

be

used above or below open-gridded
type suspended ceilings; beneath sof-
fits or beams having a depth of more
than 4 inches (101,6 mm); and, with
beams, joists, or ducts having a height
of more than 3 inches (76,2 mm) lo-
cated within the sprinkler coverage ar-
eas.

NOTE

Beams having a height of more

than 3 inches (76,2 mm) may be

located with their centerlines

along the boundaries separating

adjacent sprinkler coverage ar-

eas.

It is recommended that as part of the
sprinkler system design, the designer
review the dwelling plans and, where
appropriate, advise the owner or his
representative as to the following.

I.

Lintels of at least 3 inches (76,2

mm) in height and preferably 8

inches (203,2 mm) should be used

over all passageways from one

space to another, in order to reduce

the possibility of sprinkler opera-

tions outside of the fire area.

II.

Beams of at least 3 inches (76,2

mm) in height should be used to

border each of 5 or more adjoining

areas of F978 Sprinkler coverage

(within the same compartment), in

order to decrease the time to first

sprinkler operation as well as to

reduce the possibility of multiple

sprinkler operations.

Cold Soldering Criteria.

Figures E

and F provide the minimum spacing
requirements necessary for prevent-
ing the wetting (i.e., cold soldering) of
the heat responsive element (Bulb) of
a non-operated F978 Sprinkler, which
is adjacent to one which has operated.

Heat Source Criteria.

Refer to NFPA

13D or NFPA 13R for the requirements
relating to preventing the possible re-
lease of an F978 heat responsive ele-
ment (Bulb), due to exposure to heat
sources other than abnormal fire.

—4—

FIGURE E

SPACING RULES UNDER LEVEL CEILINGS

Figure E-1 (Plan View)

Figure E-2 (Plan View)

Figure E-3 (Plan View)

Figure E-4 (Plan View)

Figure E-5 (Plan View)

Figure E-6 (Plan View)

Figure E-7 (Plan View)

Figure E-8 (Plan View)

Figure E-9 (Elevation View)

S = THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY
CALCULATED (REF. TABLE A).

OBSOLETE

Summary of Contents for Gem F978

Page 1: ...ster board ceiling tiles etc by pushing the ceiling product against the Cap When the ceiling in stallation is complete the Cap is re moved and the Cover Plate Assembly installed The F978 Sprinklers ha...

Page 2: ...ndent Sprinklers are available in a 155 F 68 C temperature rating and they are rated for use at a maximum service pressure of 175 psi 12 1 bar The nominal installation dimensions are given in Figure A...

Page 3: ...ng jurisdiction 5 The spray from the F978 is dis tributed radially outward and downward from the sprinkler deflector Consequently the sprinklers must be located such that there will not be any blind s...

Page 4: ...in order to reduce the possibility of sprinkler opera tions outside of the fire area II Beams of at least 3 inches 76 2 mm in height should be used to border each of 5 or more adjoining areas of F978...

Page 5: ...aced a minimum of 8 feet apart d the sprinklers are installed with Deflector Arms perpendicular to the ceiling ridge and e the sprinklers shown in Figures F 1 through F 8 are located in a plane which...

Page 6: ...n kler joint should be obtained with a torque of 7 to 14 ft lbs 9 5 to 19 0 Nm More than 21 ft lbs 28 5 Nm of torque may distort the sprinkler orifice seat with consequent leakage Proceed with the ins...

Page 7: ...ing Do not screw on the Cover Plate Assembly such that it will lift a ceiling panel out of its normal position If the Cover Plate Assembly can not be engaged with the Mount ing Cup or the Cover Plate...

Page 8: ...UM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED 2 THE MOUNTING SURFACE MUST BE LOCATED WITHIN 4 TO 6 INCHES 101 6 to 152 4 mm OF THE PEAK IF IT IS NOT CONTINUOUS OVER THE...

Page 9: ...n drapes curtains or valances Do NOT hang anything from the sprinklers Automatic sprinklers are NOT to be tested with a heat source Op eration of the heat responsive element Bulb can result Do NOT cle...

Page 10: ...ainted finishes Otherwise responsibility for duplication of the de sired finish cannot be accepted Separately Ordered Parts Specify W Type 13 Sprinkler Wrench PSN 56 976 1 001 Order for NFPA publicati...

Page 11: ...11 O B S O L E T E...

Page 12: ...O B S O L E T E...

Reviews: