background image

remaining adjustment can be used to
compensate for the possible manufac-
turing variations in take-out of the fit-
ting, as well as in the make-in of the
sprinklers (as permitted by

ANSI

B1.20.1).

Step B.

After installing the F700

Mounting   Plate   over the sprinkler
threads, hand tighten the sprinkler into
the sprinkler fitting.

Step C.

Tighten the sprinkler into the

sprinkler fitting using only the W-Type
10 Recessed Sprinkler Wrench (Ref.
Figure D). With reference to Figure A,
the W-Type 10 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrenching flanges.

Step D.

After the ceiling has been in-

stalled or the finish coat has been ap-
plied, slide on the F700 Closure over

the Model F916 Sprinkler and push the
Closure over the Mounting Plate until
its flange comes in contact with the
ceiling.

CARE AND MAINTENANCE

Model F916 Sprinklers must be main-
tained and serviced in accordance
with the following instructions:

NOTE

Before closing a fire protection system

main control valve for maintenance

work on the fire protection system

which it controls, permission to shut

down the affected fire protection sys-

tem must be obtained from the proper

authorities and all personnel who

may be affected by this action must be

notified.

Absence of an escutcheon, which is

used to cover a clearance hole, may

delay the time to sprinkler operation

in a fire situation

Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.

Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.

Frequent visual inspections are rec-
ommended to be initially performed for
wax and/or lead coated sprinklers, af-
ter the installation has been com-
pleted, to verify the long term potential
integrity   of the sprinkler   coatings.
Thereafter,   annual inspections per
NFPA 25 should suffice; however, in-
stead of inspecting from the floor level,
a random sampling of close-up visual
inspections should be made, so as to
better determine the exact sprinkler
condition and the long term integrity of
the wax and/or lead coating, as it may
be affected by the corrosive conditions
present.

The owner is responsible for the in-

Dim.

Inches

MM

A-

5/8±1/8††

15,9±3,2

B-Min.

1-1/4

31,8

B-Nom.

1-1/2

38,1

B-Max.

1-3/4

44,5

C-Min.

1/4

6,4

C-Max.

3/4

19,1

MODEL F700

Dim.

Inches

MM

A-

1/2±1/4††

12,7±6,4

B-Min.

1-1/4

31,8

B-Nom.

1-5/8

41,3

B-Max.

2

50,8

C-Min.

FLUSH

C-Max.

3/4

19,1

FULLY RECESSED

DIMENSIONS†

Up to 1/2 inch adjustment from

minimum 1/4 inch to maximum

3/4 inch recessed position.

HIGH ADJUSTMENT

DIMENSIONS

Up to 3/4 inch adjustment from
the flush ceiling position to 3/4

inch recessed position.

† For best overall appearance.

†† Remaining 1/4 inch (6,4 mm) of

adjustment can be used to compensate
for variations in sprinkler make-in and
fitting take-out.

1- Model F916 Pendent Sprinkler
2- Model F700 Recessed Escutcheon

a- Mounting Plate
b- Closure

FIGURE B

2.8 K-FACTOR MODEL F916 RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE MODEL F700 RECESSED ESCUTCHEON

FIGURE C

W-TYPE 9 SPRINKLER WRENCH

WRENCH

RECESS

FIGURE D

W-TYPE 10 RECESSED

SPRINKLER WRENCH

OBSOLETE

Reviews: