TFP313

Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP.  All rights reserved.

Care and 

Maintenance

 TYCO Model ESFR-22 Pendent Sprin-

klers must be maintained and serviced 

in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. 
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Asso-

ciation (e.g., NFPA 25), in addition to 

the standards of any authorities having 

jurisdiction. Contact the installing con-

tractor or product manufacturer with 

any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Sprinkler Assemblies

Specify: Model ESFR-22 (TY8226), 

K=22.4, Early Suppression, Fast 

Response Pendent Sprinkler with 

(specify) temperature rating, Natural 

Brass, P/N (specify):

165°F (74°C) . . . . . . . . . . . . . . . . . . 58-459-1-165 

205°F (96°C). . . . . . . . . . . . . . . . . . 58-459-1-205

Special Order 

Sprinkler Assemblies with 

ISO 7-1 Thread Connections

Specify: Model ESFR-22 (TY8226), 

K=22.4, Early Suppression, Fast 

Response Pendent Sprinkler with 

ISO 7-1 thread connection, (specify) 

temperature rating, Natural Brass, 

P/N (specify):

165°F (74°C) . . . . . . . . . . . . . . . . . . 58-460-1-165 

205°F (96°C). . . . . . . . . . . . . . . . . .58-460-1-205

Sprinkler Wrench

Specify: W-Type 32 Sprinkler Wrench, 

P/N 56-001-1-459

OBSOLETE

Summary of Contents for ESFR-22

Page 1: ...addition to the standards of any authorities having jurisdiction e g FM Global Failure to do so may impair the performance of these devices The owner is responsible for maintaining their fire protection system and devices in proper operating condition Contact the installing contractor or product manufacturer with any questions In all cases the appropriate NFPA or FM installation standard or other ...

Page 2: ...andard Refer to NFPA 13 Chapter 19 Refer to FM Global 8 21 Flammable Ignitable Liquid Storage Refer to the Standard Refer to NFPA 30 Refer to FM Global 7 29 Aerosol Storage Refer to the Standard Refer to NFPA 30B Refer to FM Global 7 31 Automotive Components in Portable Racks Control mode only refer to the Standard N A N A N A Not Applicable 1 NPT Hook 4 7 8 5 6 Link Assembly Sealing Assembly Butt...

Page 3: ...g Distance NFPA 6 to 18 inches 152 to 457 mm Centerline of Thermal Sensing Element to Ceiling Distance FM Global See FM Global 2 0 for Storage Sprinklers Operation The fusible link assembly is com prised of two link halves that are joined together by a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate activating the sprinkler and flowing w...

Page 4: ... or the like must be replaced The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards of any authorities having jurisdiction Contact the installing con tractor or product manufacturer ...

Reviews: