Model ESFR-22
22.4 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Page 1 of 4
DECEMBER 2015
TFP313
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1 inch NPT or
ISO 7-R 1
Discharge Coefficient
K=22.4 gpm/psi
1/2
(320 lpm/bar
1/2
)
Temperature Ratings
165°F (74°C)
205°F (96°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Strut. . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Button
. . . . . . . . . . . . . . Copper, Stainless Steel
Sealing Assembly . . . . . . . . . . . . Nickel w/PTFE
Applications for the TYCO ESFR Sprin-
klers are expanding beyond currently
recognized installation standards. For
information on research fire tests (e.g.,
with flammable liquids and aerosols)
that may be acceptable to an author-
ity having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-22 Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(NFPA), in addition to the standards of
any authorities having jurisdiction (e.g.,
FM Global). Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product
manufacturer with any questions.
In all cases, the appropriate NFPA or FM
installation standard, or other applicable
standard, must be referenced to ensure
applicability and to obtain complete
installation guidelines. The general
guidelines in this technical data sheet
are not intended to provide complete
installation criteria.
Sprinkler
Identification
Number (SIN)
TY8226
General
Description
TYCO Model ESFR-22 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 22.4 (Ref. to Figure 1). They
are suppression-mode sprinklers that
are especially advantageous as a
means of eliminating the use of in-rack
sprinklers when protecting high-piled
storage.
The Model ESFR-22 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• some storage arrangements of
rubber tires, roll paper, flammable
liquids, and aerosols
For more specific criteria, refer to Table
1 as well as the applicable design
standard.
The Model ESFR-22 can protect a
storage arrangement of 40 ft. (12,2 m)
with a ceiling height of 45 ft. (13,7 m)
without requiring in-rack sprinklers.
In addition, it can be installed with a
maximum deflector-to-ceiling distance
of 18 inches (460 mm).