Model ESFR-22

22.4 K-factor Pendent Sprinklers 

Early Suppression, Fast Response

Page 1 of 4 

DECEMBER 2015 

TFP313

IMPORTANT

Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connections

1 inch NPT or 

ISO 7-R 1

Discharge Coefficient

K=22.4 gpm/psi

1/2

 (320 lpm/bar

1/2

)

Temperature Ratings

165°F (74°C) 

205°F (96°C)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . .  Stainless Steel

Hook  . . . . . . . . . . . . . . . . . . . . . . Stainless Steel 

Strut. . . . . . . . . . . . . . . . . . . . . . .  Stainless Steel 

Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel

Button

  . . . . . . . . . . . . . . Copper, Stainless Steel

Sealing Assembly . . . . . . . . . . . .  Nickel w/PTFE 

Applications for the TYCO ESFR Sprin-

klers are expanding beyond currently 

recognized installation standards. For 

information on research fire tests (e.g., 

with flammable liquids and aerosols) 

that may be acceptable to an author-

ity having jurisdiction, contact Tyco Fire 

Protection Products (TFPP) Technical 

Services.

NOTICE

The Model ESFR-22 Sprinklers described 

herein must be installed and maintained 

in compliance with this document, as 

well as with the applicable standards of 

the National Fire Protection Association 

(NFPA), in addition to the standards of 

any authorities having jurisdiction (e.g., 

FM Global). Failure to do so may impair 

the performance of these devices.
The owner is responsible for maintaining 

their fire protection system and devices 

in proper operating condition. Contact 

the installing contractor or product 

manufacturer with any questions.
In all cases, the appropriate NFPA or FM 

installation standard, or other applicable 

standard, must be referenced to ensure 

applicability and to obtain complete 

installation guidelines. The general 

guidelines in this technical data sheet 

are not intended to provide complete 

installation criteria.

Sprinkler 

Identification 

Number (SIN)

TY8226

General 

Description

TYCO Model ESFR-22 Pendent Sprin-

klers are Early Suppression, Fast 

Response Sprinklers having a nominal 

K-factor of 22.4 (Ref. to Figure 1). They 

are suppression-mode sprinklers that 

are especially advantageous as a 

means of eliminating the use of in-rack 

sprinklers when protecting high-piled 

storage.
The Model ESFR-22 Sprinklers are pri-

marily used for ceiling-only sprinkler 

protection of (but not limited to) the 

following storage applications:
•  most encapsulated or non-encap-

sulated common materials including 

cartoned, unexpanded plastics

•  uncartoned (exposed) expanded 

plastics in accordance with NFPA 13 

and FM Global standards

•  some storage arrangements of 

rubber tires, roll paper, flammable 

liquids, and aerosols

For more specific criteria, refer to Table 

1 as well as the applicable design 

standard.
The Model ESFR-22 can protect a 

storage arrangement of 40 ft. (12,2 m) 

with a ceiling height of 45 ft. (13,7 m) 

without requiring in-rack sprinklers. 

In addition, it can be installed with a 

maximum deflector-to-ceiling distance 

of 18 inches (460 mm).

OBSOLETE

Summary of Contents for ESFR-22

Page 1: ...addition to the standards of any authorities having jurisdiction e g FM Global Failure to do so may impair the performance of these devices The owner is responsible for maintaining their fire protection system and devices in proper operating condition Contact the installing contractor or product manufacturer with any questions In all cases the appropriate NFPA or FM installation standard or other ...

Page 2: ...andard Refer to NFPA 13 Chapter 19 Refer to FM Global 8 21 Flammable Ignitable Liquid Storage Refer to the Standard Refer to NFPA 30 Refer to FM Global 7 29 Aerosol Storage Refer to the Standard Refer to NFPA 30B Refer to FM Global 7 31 Automotive Components in Portable Racks Control mode only refer to the Standard N A N A N A Not Applicable 1 NPT Hook 4 7 8 5 6 Link Assembly Sealing Assembly Butt...

Page 3: ...g Distance NFPA 6 to 18 inches 152 to 457 mm Centerline of Thermal Sensing Element to Ceiling Distance FM Global See FM Global 2 0 for Storage Sprinklers Operation The fusible link assembly is com prised of two link halves that are joined together by a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate activating the sprinkler and flowing w...

Page 4: ... or the like must be replaced The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards of any authorities having jurisdiction Contact the installing con tractor or product manufacturer ...