General
Description

The

Series

RFII, 5.6 K-Factor, Ex-

tended Coverage, Light Hazard
(ECLH) “Royal Flush II” Concealed
Pendent Sprinklers are decorative, 3
mm bulb type sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as hotel
lobbies, office buildings, churches,
and restaurants.
They are intended for use in automatic
sprinkler systems designed in accord-
ance with standard installation rules
(e.g., NFPA 13). The fast response
thermal sensitivity rating of the Series
RFII (TY3532) provides for a quick re-
sponse extended coverage (QREC)
rating up to an 18 ft. x 18 ft. coverage
area.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 1/2
inch (12,7 mm) of vertical adjustment,
to reduce the accuracy to which the
length of fixed pipe drops to the sprin-
klers must be cut.
The Series RFII

Sprinklers are

shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed  for  installation, and  then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark

the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.

WARNINGS

The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to  the standards of any
other authorities having  jurisdiction.
Failure to do so may impair the integ-
rity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Model/Sprinkler
Identification
Numbers

TY3532

Technical
Data

Approvals

UL and C-UL Listed.
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
NYC under MEA 353-01-E.

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,6 LPM/bar

1/2

)

Temperature Ratings

155F/68C Sprinkler - 135F/57C Plate
200F/93C Sprinkler - 165F/74C Plate

Adjustment

1/2 inch (12,7 mm)

Finishes

Cover Plate: Chrome Plated,  Brass
Plated, or White Painted (Custom paint
matches and colors other than white
are available on request.)

Physical Characteristics

Frame

. . . . . . . . . . . . Bronze

Support Cup . . Chrome Plated Steel
Guide Pins . . . . . . Stainless Steel
Deflector . . . . . . . . . . . Bronze
Compression Screw . . . . . . Brass
Bulb

. . . . . . . . . . . . . . Glass

Cap . . . . . . . . Bronze or Copper
Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon*

Cover Plate

. . . . . . . . . . Brass

Retainer . . . . . . . . . . . . Brass
Ejection Spring

. . . Stainless Steel

Patents

U.S.A. Patent Number 4,014,388 may
be applicable to the Series RFII
(TY3532) Concealed Pendent Sprin-
klers. Other patents are pending with
regard to other design features.

Series RFII — 5.6 K-factor
“Royal Flush II” Pendent Concealed Sprinklers
Quick & Standard Response, Extended Coverage

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

Page 1 of 4

TFP260

FEBRUARY, 2002

Customer Service/Sales:

Tel: (215) 362-0700 / (800) 523-6512

Fax: (215) 362-5385

TFP260 (2-8.1)

OBSOLETE

Summary of Contents for CENTRAL RFII Series

Page 1: ...ct against the Protective Cap When the ceiling in stallation is complete the Protective Cap is removed and the Cover Plate Assembly installed WARNINGS The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compli ance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any...

Page 2: ...e obtained with a torque of 7 to 14 ft lbs 9 5 to 19 0 Nm A maxi mum of 21 ft lbs 28 5 Nm of torque is to be used to install sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leak age or impairment of the sprinkler Do not attempt to compensate for in sufficient adjustment in the Sprinkler Assembly by under or over tightening the Sprinkler Support Cup Assembly Readj...

Page 3: ...ntil its flange just comes in contact with the ceiling Do not continue to screw on the Cover Plate Retainer Assembly such that it lifts a ceiling panel out of its normal position If the Cover Plate Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate Re tainer Assembly cannot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned TFP260 Pag...

Page 4: ...ntained by a qualified Inspection Service Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date of ship ment by Tyco Fire Products No war ranty is given for ...