©1998 Central Sprinkler Company
   Printed in U.S.A.

collar, thereby drawing the
escutcheon (and closure plate) tight
against the mounting surface. The
tamper resistant retaining screws can
only be installed or removed with the
special tamper-proof socket.
Caution:    Special care must be taken
when installing with a CPVC system
to ensure that no primer or cement
accumulates within the sprinkler.
     Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler drop and
associated fittings have been wire
brushed to remove any flux.
Residual flux can cause corrosion
and in extreme cases can impair
proper sprinkler operation.

qualified inspection service.  Length
of time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.

Do not attempt to reassemble or

otherwise reuse a sprinkler that has
operated.  Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.

Because the discharge pattern is

critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern.  Such
obstructions must be removed.  In the
event that construction has altered
the original configuration, additional
sprinklers may need to be installed to
maintain protection level.

Do not attempt to replace sprinklers

without first removing the fire protec-
tion system from service.  Be certain
to secure permission from all 

Authori-

ties Having Jurisdiction, and notify all
personnel who may be affected
during system shutdown. A fire watch
during maintenance periods is a
recommended precaution.

To remove the system from service

mode, first refer to the system
operating guide and valve instruc-
tions.  Drain water and relieve
pressure in the pipes.  Remove the
existing unit and install the replace-
ment, using only the special sprinkler
wrench.  Be certain to match model,
style, orifice, and temperature rating.

A fire protection system that has

been shut off after activation should
be returned to service immediately.
Inspect the entire system for damage
and replace or repair as necessary.
Sprinklers that did not operate but
were subjected to corrosive elements

of combustion or excessive tempera-
tures should be inspected, and
replaced if need be. The 

Authority

Having Jurisdiction will detail mini-
mum replacement requirements and
regulations.

Guarantee:  Central Sprinkler

Company will repair and/or replace
any product found to be defective in
material or workmanship within a
period of one year from date of
shipment.  Please refer to the current
Price List for further details of the
warranty.

Ordering Information:  When

placing an order, indicate the full
product name.  Please specify the
quantity, model number, style, orifice
size, temperature rating, sprinkler
finish, escutcheon finish, closure
plate(s) and finish, and sprinkler
wrench.

For special painted escutcheon

finishes, it is advisable to provide
quick-dry paint preferably in a lacquer
base finish to ensure proper color
duplication. Without such a guide,
Central Sprinkler Company cannot be
responsible for acceptable color
matching.

Availability and Service:  Central

sprinklers, valves, accessories, and
other products are available
throughout the U.S. and Canada, and
internationally, through a network of
Central Sprinkler Company distribution
centers. You may write directly to
Central Sprinkler Company or call
(215) 362-0700 for the distributor
nearest you.

Patents:  The Omega Prohibitor™

QR Automatic Sprinklers are protected
under U.S. Patent No. 4,491,182.
Additional patents are pending.

Conversion Table:

1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 Kpa

= 0.0689 bar
= 0.0703 kg/cm

2

1 U.S. gallon = 3.785 dm

3

= 3.785 liters

Conversions are approximate.

Ordering
Information

PRO-QR3

Care &
Maintenance

Sprinklers must be handled care-

fully.  They must not be transported
or stored where ambient tempera-
tures may exceed 100

o

F/38

o

C. For

best results, store them in a cool, dry
location in the original shipping
package.

Do not install sprinklers that have

been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such a manner
must be replaced.

The owner is responsible for the

proper working condition of all fire
protection devices and accessories.
The NFPA Standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems” contains guidelines and
minimum maintenance requirements.
Furthermore, the local 

Authority

Having Jurisdiction may have addi-
tional regulations and requirements
for maintenance, testing, and inspec-
tion that must be obeyed.

It is advisable to have sprinkler

systems inspected regularly by a

Central Sprinkler Company