Tyco Fire Product CENTRAL ELO-231 Instruction Manual Download Page 2

Temperature Rating: 165

°

F/74

°

C

212

°

F/100

°

C

286

°

F/141

°

C

Hydraulic Design Criteria:   The density required is

0.60 gpm/sq. ft. (24,5 mm/min).

Design Area:

For wet systems 2000 sq. ft. (186 m

2

)

and for dry systems use 2600 sq. ft.
(242 m

2

)

Spacing:

Maximum spacing is 100 sq. ft.
(9,3 m

2

).  The maximum distance

between sprinklers is 12'-0" (3,7 m) -
12'-6"(3,8 m) spacing is allowed in
25'-0"(7,6 m) bays.  Minimum spacing
is 6'-0" (1,8 m) apart unless
separated by baffles.

Obstructions:

NFPA criteria for standard spray
sprinklers.

Type of Storage:  Single, double, multiple-row and

portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.

Commodity:  Class I-IV, encapsulated or non-

encapsulated.  Group A and B plastics -
cartoned, expanded or unexpanded as
well as exposed, unexpanded.

Maximum Storage Height: 20'-0" (6,1 m)

Clearance:

36" (0,9 m) minimum from deflector
to top of storage.

Max. Ceiling Height in Area of Storage: 25'-0" (7,6 m)

Construction Type:  All types - deflector distances per
                                   NFPA 13.

System Type:      Wet or dry

Table 2 - ELO-231 UL & ULC Specific Application Guidelines

Figure 2 - ELO-231, Pendent Sprinkler

Figure 1 - Model ELO-231, Upright Sprinkler

1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters Laboratories, Inc. for  maximum
   150

°

F/68

°

C ambient temperatures.

3. Listed by Underwriters' Laboratories of Canada.
4. Approved by Factory Mutual Research Corporation.

Table 1 - Laboratory Listings and Approvals (11.2 K-factor Sprinklers with 1/2" or 3/4" NPT)

Notes:

5. Approved by Factory Mutual Research Corporation for
    maximum 150

°

F/68

°

C ambient temperatures.

6. Approved by the City of New York under MEA 127-93-E

* Upright Only

            SPRINKLER FINISH

           Pendent and Upright

Temperature

    Frame

Natural       Chrome         Lead          Wax

  Wax Over

     Rating

Color Code

 Brass        Plated        Coated        Coated      Lead Coated

    165

°

F/74

°

C

   Unpainted

    212

°

F/100

°

C

       White

    286

°

F/141

°

C

        Blue

CENTRAL

1-7/8 

(47,6 mm)

WRENCH

FLAT

ELEVATION VIEW

2-13/16"

(71,4 mm)

7/16" 

(11,1 mm)

1/2" or

3/4" NPT

CENTRAL

WRENCH

FLAT

ELEVATION VIEW

7/16" 

(11,1 mm)

3/4" NPT

2-7/8"

(73,0 mm)

1-3/16"

(30,2 mm)

1-11/16"

(42,9 mm)

1,3,4,6

        1,3,4,6               1,4*              1,4*

       1,4*

1,3,4,6

        1,3,4,6

     1,4*              1,4*

       1,4*

1,3,4,6

        1,3,4,6

     1,4*              2,5*

       2,5*

OBSOLETE