having jurisdiction. Failure to do so
may impair the integrity of these
devices.

Because of the above cited stipula-
tions and the varied nature of
residential type architecture, there
will be some compartment designs
which cannot be fully sprinklered in
accordance with the recomendations
of NFPA 13, NFPA 13D, or
NFPA 13R. In the event of this
condition, consult the authorities
having jurisdiction for guidance
and approval.

The owner is responsible for
maintaining their fire protection
system and devices in proper
operating condition. The installing
contractor or sprinkler manufac-
turer should be contacted relative
to any questions.

Sprinkler Identification Number
SIN C3296

Approvals
UL & ULC Listed. NYC Approved
(Refer to the Design Criteria Section)

Maximum Working Pressure
175 psi (12,1 bar)

Pipe Thread Connection
1/2 inch NPT

Discharge Coefficient
K = 5.3 GPM/psi

1/2

 (76,3 LPM/bar

1/2

)

Temperature Ratings
155

°

F/68

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass

Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model BV-R1

No. 4-3.5

5.3 K-factor -
Fast Response Residential

Pendent & Recessed Pendent Glass Bulb Automatic Sprinkler

General
Description

The Central Model BV-R1, 5.3
K-factor Residential Pendent and
Recessed Pendent sprinklers are
decorative glass bulb sprinklers
designed for use in residential
occupancies such as homes, apart-
ments, dormitories, and hotels.

They are to be used in wet pipe
residential sprinkler systems for one-
and two-family dwellings and mobile
homes per NFPA 13D; wet pipe
residential sprinkler systems for
residential occupancies up to and
including four stories in height per
NFPA 13R; or, wet pipe sprinkler
systems for the residential portions of
any occupancy per NFPA 13.

The recessed version of the Model
BV-R1 Residential Pendent Sprinkler
is obtained by utilizing the Model
BV-R1 Residential Pendent Sprinkler
in combination with the Model BV
Res./QR Recessed Escutcheon
Assembly.  The recessed version of
the Central Model BV-R1 using a
Model BV Res./QR Recessed
Escutcheon provides up to  3/8 inch
(9,5 mm) of total adjustment from the
flush pendent position.

Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently
to shatter the glass bulb, which then
allows the sprinkler to activate and
flow water.

WARNING

The BV-R1 Residential Pendent
Sprinklers described herein must
be installed and maintained in
compliance with this document, as
well as with the applicable stan-
dards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities

Technical
Data

CENTRAL

BV-R1

7-02

Residential
Pendent and
Recessed
Pendent
Sprinklers

Physical Characteristics
The Model BV-R1 Residential
Pendent Sprinkler utilizes a dezincifi-
cation resistant (DZR) bronze frame
and a 3 mm bulb. The sprinkler frame
orifice is sealed with a  gasketed
spring plate (Belleville Seal) consist-
ing of a beryllium nickel disc spring
that is sealed on both its inside and
outside edges with a Teflon

TM

 gasket.

The compression screw is bronze,
and the deflector is brass.

SPRINKLERS FOR REPLACEMENT USE ONLY IN EXISTING SPRINKLER SYSTEMS

OBSOLETE

Summary of Contents for CENTRAL BV-R1

Page 1: ...ls They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to...

Page 2: ...Pendent UL Specific Application Sloped Ceiling Hydraulic Design Requirements for NFPA 13D NFPA 13R Occupancies For use with Figure 4 Table 1 BV R1 Pendent Recessed Pendent Hydraulic Design Requirement...

Page 3: ...and with pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Wrench tighten the sprinkler using only a BV Sprinkler Wrench 1099 Ref Figure 3 T...

Page 4: ...inimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B 8 0...

Page 5: ...he minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 13 If Acceptable Figure 11 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...s Obstructed 10 15 20 25 30 35 40 45 Acceptable 20 x 20 18 x 18 16 x 16 14 x 14 12 x 12 The Central Model BV R1 must be maintained and serviced in accordance with the following instructions NOTES Wet...

Page 8: ...standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler manufacturer should b...

Reviews: