12

Printed in U.S.A. 3-01

Ordering Information:  When placing
an order, indicate the full product
name.  Please specify the quantity,
model, style, orifice size, temperature
rating, type of finish or coating, and
sprinkler wrench. Refer to price list for
complete listing of Part Numbers.

Patents: U.S.A. Patent Number
5,669,449 is applicable to the Central
Specific Application Attic Sprinklers.
Other Patents are pending with regard
to other design features.

Teflon is a trademark of the DuPont Corp.

Ordering
Information

Flow Control

T y c o   F i r e 

P r o d u c t s

The Specific Application Attic Sprin-
klers must be maintained and ser-
viced in accordance with the following
instructions.

NOTES

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system it
controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties.  All personnel who may be
affected by this action must be
notified.

Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.

Automatic sprinklers must never be
shipped or stored where their tem-
peratures will exceed 100

°

F/38

°

C and

they must never be painted, plated,
coated or otherwise altered after
leaving the factory. Modified, or over-
heated fusible link sprinklers must be
replaced.  Glass Bulb sprinklers that
have been exposed to corrosive
products of combustion, but have not
operated, should be replaced if they
cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion Section).

The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Care &
Maintenance

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufactured
by companies not affiliated by owner-
ship with Tyco Fire Products or for
products and components which have
been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of products
or parts of products. Tyco Fire
Products shall not be responsible for
sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY EX-
CEED AN AMOUNT EQUAL TO THE
SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.

Limited
Warranty

OBSOLETE

Summary of Contents for CENTRAL Attic

Page 1: ...the 60 second requirement to be met without an accelerator The other cost reduction is in the new Listing of BlazeMaster CPVC for Attic spaces feeding the wet system sprinklers below the ceiling Tradi...

Page 2: ...monel thermal sensitive link The sprinkler frame orifice is sealed with a gasketed spring plate Belleville Seal consisting of a beryllium nickel disc spring that is sealed on both its inside and outs...

Page 3: ...N VIEW 2 50 8 mm 1 2 NPT WRENCH FLAT ELEVATION VIEW Back to Back Dual Directional Attic Sprinkler BB1 17 32 BB2 17 32 BB3 17 32 Back to Back Dual Directional Attic Sprinkler BB1 BB2 BB3 HIP Sprinkler...

Page 4: ...area above must be protected by Attic Sprinklers see figure 10 Insulation is for fire protection purposes It is not freeze protection BlazeMaster CPVC must be installed in accordance with the BlazeMas...

Page 5: ...5mm than 10 3 0 m SD2 30 9 1 m to more 25 95 20 0 1 4 7 12 178mm 305mm to less than 10 12 254 mm 305mm than 10 3 0 m SD3 30 9 1 m to more 25 95 20 0 1 4 10 12 254mm 305mm to 12 12 305mm 305mm than 10...

Page 6: ...kler Single Directional Attic Sprinkler Single Directional Attic Sprinkler Span Dimension Single Directional 16 406 4 mm minimum 22 558 8 mm maximum To Bottom of Sheathing Branch Line Ceiling Truss Ri...

Page 7: ...the maximum spacing is 6 0 1 8 m and the minimum is 4 0 1 2 m see figures 2 11 The reason 400 square feet is not an issue with the single directional is because at its maximum spacing 6 0 1 8 m on cen...

Page 8: ...ee figure 12 for joists perpendicular to outside wall Ridge Single Directional Attic Sprinkler Outside Wall 40 0 12 2 m maximum 3 0 0 9 m max on slope Back to Back Attic Sprinkler 6 0 1 8 m Max 6 0 1...

Page 9: ...be 6 152 4mm clearance over the top of the obstruction to allow water to pass both over and under the obstruction The 6 152 4mm is measured perpendicular to the slope from the bottom of the joist If t...

Page 10: ...rio To use attic sprinklers in these attics space attic sprinklers to protect the center portion of the building add standard sprinklers around the perimeter at a maximum of 7 0 2 1m and a minimum of...

Page 11: ...tics having a mixture of standard spray sprinklers and Specific Application Attic SprinklersTM The design area requirements of NFPA 13 shall apply to all sprinkler types 5 Attics having a Width Greate...

Page 12: ...ith the appli cable standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler m...