Chapter 1 Alarm Interface Cabling
PDAP-15A Power Alarm Connections
Release TR3.2.1
Turin Networks
Page 9-21
PDAP-15A
Power Alarm
Connections
Follow these steps to complete power alarm connections at PDAP-15A.
Important:
Always wear a properly Electrostatic Discharge (ESD) wrist
strap when making alarm wire connections to the PDAP-15A.
Table 9-12 Connect PDAP-15A Power Alarms
Step
Procedure
1
Two alarm wires are required for Power alarms, normally-open (NO) and
common (C) or normally-closed (NC) and common (C). Strip back the
insulation by 3/4 inch (19 mm) exposing enough wire to make a minimum
of five turns.
2
Power alarm wires are connected to wire-wrap posts on the back of the
PDAP-15A. Terminate the power alarm wires using a wire-wrap tool.
Figure 9-16 PDAP-15A Power Alarm Input Wire-Wrap Posts
3
Route power alarm wires to the CO power alarm panel following local
procedures.
4
Connect power alarm wires to the external or CO power alarm panel
following local procedures.
Note:
Two wires are required for the power alarm (normally-open and
common or normally-closed and common).
5
The Connect PDAP-15A Power Alarms procedure is complete. Continue
to the Connect PDAP-15A Fuse Alarms procedure.