Commissioning
Connecting the device to a Modbus master
72
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.7
Connecting the device to a Modbus master
In this example, the
Continuous mode active
bit has to be set. This requires the network inter-
face to be set up, the hardware configured and the I/O mapping defined.
Hardware used
This example uses the following hardware components:
n
Turck HMI TX707-P3CV01 (Modbus master)
n
TN-UHF-Q300-EU-CDS UHF read/write head (IP address: 192.168.1.20)
Software used
This example uses the following software:
n
CODESYS 3.5.12.1 (download free of charge from
)
Prerequisites
n
The programming software has been started.
n
A new project has been created.
n
The PLC has been added to the project.
Summary of Contents for TN-UHF AUS-CDS Series
Page 1: ...Your Global Automation Partner Instructions for Use TN UHF CDS UHF Read Write Head ...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Page 97: ...V02 00 2020 08 97 Transfer the mapping to the POU Fig 94 Transferring the mapping to the POU ...