19
2018/02
TBIP-L…-FD
IO1-2
IOL- Safe I/
O chann
e
ls
3.4.4
Technical data – safety outputs
3.4.5
Derating curves
Safety outputs
Suitable for inputs according to EN 61131-2, type 1
Output level in OFF-state
Voltage level
< 5V
Current level
< 1 mA
Test pulses
ohmic load, maximum
0.5 ms
maximum
1.25 ms
Interval between two test pulses
typical
500 ms
minimum
250 ms
The load has to provide a mechanical or electrical inertia in order to tolerate the test pulses.
Max. output current
DC load
2 A, derating see
DC13 load without external free-wheeling diode
1 A
DC13 load with external free-wheeling diode
2 A
Max. total current for device
9 A, derating see
Times
Internal delay time
(for calculating the Watchdog time)
10 ms
Reaction times
see
Safety Characteristic Data (page 16)
Max. output current, DC load
Max. total current for device
Fig. 4: Derating curves
I
[A]
[°C]
1.5
0
-40
40
70
2
0
∑ I
[A]
[°C]
7
0
-40
40
70
9
0