Technical data
144
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
15
Technical data
Technical Data
Power supply
Supply voltage
24 VDC
Permissible range
18…30 VDC
n
IO-Link
n
20,4 ... 28.8 VDC
Total current
Max. 9 A per voltage group
V1 + V2 max. 11 A
Operating current
< 120 mA
Sensor/actuator supply V
AUX1
Supply from V1 short-circuit proof,
max. 4 A per connector C0 und C4,
max. 2 A per connector C1…C3, C5…C7
Sensor/actuator supply V
AUX2
Class B supply from V2 short-circuit proof,
max. 4 A per connector C4…C5
max. 2 A per connector C6…C7
Potential isolation
Galvanic isolation from V1 and V2 voltage group, voltages
up to 500 VDC
Connectors
Ethernet
2 x M12, 4-pin, D coded
Power supply
n
TBEN-L4-…
n
X1: 7/8“ male connector, 4-pole
n
X2: 7/8“ female connector, 4-pole
n
TBEN-L5-…
n
X1: 7/8“ male connector, 5-pole
n
X2: 7/8“ female connector, 5-pole
Digital in-/outputs
Permissible torques
n
Ethernet
n
I/O channels/supply
n
Mounting (M6 screws)
0.6 Nm
0.8 Nm
1.5 Nm
Isolation voltages
V1 to V2
≥ 500 V AC
V1/V2 to field bus
≥ 500 V AC
System data
Transmission rate
10 Mbps/100 Mbps
Fieldbus connection technology
2 x M12, 4-pole, D coded
Protocol detection
Automatic
Web server
Integrated, 192.168.1.254
Service interface
Ethernet via P1 or P2
Field Logic Controller (FLC)
Supported from firmware version
3.0.6.0
Released as of ARGEE version
2.0.25.0
Modbus TCP
Address assignment
Static IP, DHCP
Supported Function Codes
FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of TCP connections
8