turck PSU67-3P-1H2-1H0-24250 Quick Start Manual Download Page 4

The device is designed, tested and approved for branch circuits up to 20 A 

(UL) and 32 A (IEC) without additional protection device. 

 

If an external fuse is used, use B or C characteristic circuit breakers with at 

least 6 A to avoid a nuisance tripping of the circuit breaker.

Operating

CAUTION

Hot surfaces

Burn risk

Do not touch the housing during operation or shortly after power-off.

The green Status LED reports an output above 90 % of the adjusted voltage. 

Relay OK contact

The Relay OK contact (ROK, s. fig. 3) monitors the output voltage. The contact 

is closed, the Status LED green lights up green. 

Contact ratings: 

 

60 VDC: 0.3 A 

 

30 VDC: 1 A 

 

30 VAC: 0.5 A for resistive loads

The device is safe in case of a single phase loss.  An external protection is not 

necessary.  

LED bargraph and push-buttons

 

Monitoring mode (normal operation)  

Actual output power = percentage of max. 500 W (100 % = 500 W)  

Values above 100 % are shown in orange. 

 

Configuration mode

Button [Voltage Set]

Hold for 3 s Configuration mode, all LEDs flash shortly.

The currently set output voltage is displayed via the LED bar.

Hold for 1 s Mode ”Set output voltage” 

Set the output voltage by using the 

[

] [

 buttons.

Buttons [

] [

]

Set value

The set value for output voltage or tripping current is indicated via 
the LED bar.  All orange LEDs are off.  The setting becomes effective 
immediately.

Without further pressing of push-buttons, the LED bar will return from any 

other mode to normal mode after 15 s.

All values are typical figures specified at 3 × 400 VAC, 50 Hz input voltage, symmetrical 

phase voltages, 24 V, 500 W output load, 25 °C ambient temperature and after a 5 

minutes run-in time unless specified otherwise.
Type designation

PSU67-3P-1H2-1H0-24250

ID

100028239

Output

Output voltage

24 VDC, nominal value

Adjustment range

24…28 VDC

Output power 24…28 V, continuous at ambient temperature:

 

– at 45 °C

600 W

 

– at 55 °C

500 W

 

– at 70 °C

350 W

Max. output power (P

max

)

 

, short-term, up to 5 s at ambient temperature

 

– up to 55 °C

1000 W

 

– at 70 °C

700 W

Linear derating b45 °C and +70 °C (s. fig. 5)
Rated current

20.8 A

Input

Input voltage AC

3 AC, 380…480 V ±15 %

Mains frequency

50…60 Hz ±6 %

Input current AC

1.1/0.9 A at 3 × 400/480 VAC

Power factor

0.94/0.95 at 3 × 400/480 VAC

Input inrush current

1.5/1.5 A peak at 3 × 400/480 VAC,  

temperature independent

Efficiency

Efficiency

95.8/95.6 % at 3 × 400/480 VAC

Losses

20.8/23.0 W at 3 × 400/480 VAC

Hold-up time

 24/24 ms at 3 × 400/480 VAC

Ambient conditions

Temperature range

-25…+70 °C

Max. ambient temperature

+70 °C, measured 2 cm below the device

Relative humidity

5…95 % 

Housing

Dimensions (l × w × h)

182 × 183 × 59 mm, without connectors

Weight

1200 g/2.7 lb

Protection class

IP65/IP67, with all mating connectors 

firmly connected

Technical data

Maintenance

Clean the devices at regular intervals with a damp cloth.

Repair

The device must not be repaired by the user. Take defective devices out of 

operation. Observe our return acceptance conditions when returning the 

device to Turck.

Disposal

The devices must be disposed of correctly and must not be included in 

normal household garbage.

EN

Quick Start Guide

Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | [email protected] | www.turck.com

© Hans Turck GmbH & Co. KG | 100034423 2022-02

PSU67-3P-1H2-1H0-24250

-25

0

+45

+70

+55

P

Out

/W

T

/°C

0

1000

350

500

600

700

B

A

A: continuous

B: short term (max. 5 s)

Wiring diagrams

2

1

3

5

4

1 = L1

2 = L2

3 = L3

4 = n.c.

5 = PE

2
3

1
4

1 = n.c.

2 = GND

3 = 24 VDC

4 = n.c.

v

Input HanQ4/2

Output HanQ4/0

1 = RELAY +

2 = n.c.

3 = n.c.

4 = RELAY - 

5 = n.c.

3

4

1

2

5

M12 Relay-OK