Setting
Setting via teach adapter
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V03.00 | 2022/08 | 21
9.1.4
Activating the teach lock
NOTE
The teach lock function is deactivated on delivery.
Supply the device with voltage.
Bridge pin 5 and pin 1 for 30 s.
a
LED 2 initially flashes green for 2 s, then lights up green continuously for 8 s, flashes
green again (after a total of 10 s) and flashes green (after a total of 30 s) at a higher
frequency.
a
The teach lock function of the sensor is activated.
9.1.5
Deactivating teach lock
Supply the device with voltage.
Bridge pin 5 and pin 1 for 30 s.
a
LED 2 lights up green continuously for 30 s (teach lock is still activated) and after 30 s
flashes green at a higher frequency.
a
The teach lock function of the sensor is deactivated.
9.2
Setting via teach adapter
9.2.1
Setting the measuring range
Supply the device with voltage.
Place the positioning element at the zero point of the measuring range.
Teach-in the pushbutton on the adapter for 2 s against GND.
a
LED 2 flashes green for 2 s and then lights up green continuously.
a
The zero point of the measuring range is stored.
Supply the device with voltage.
Place the positioning element at the end point of the measuring range.
Teach-in the pushbutton on the adapter for 2 s against U
B
.
a
LED 2 flashes green for 2 s and then lights up green continuously.
a
The zero point of the measuring range is stored.
9.2.2
Reset the sensor to the factory settings
Supply the device with voltage.
Teach-in the pushbutton on the adapter for 10 s against U
B
.
a
LED 2 initially flashes green for 2 s, then lights up green continuously for 8 s and flashes
green again (after a total of 10 s).
a
The sensor is reset to the factory setting.
9.2.3
Reset the sensor to the inverted factory settings
Supply the device with voltage.
Teach-in the pushbutton on the adapter for 10 s against GND.
a
LED 2 initially flashes green for 2 s, then lights up green continuously for 8 s and flashes
green again (after a total of 10 s).
a
The sensor is reset to the inverted factory setting.