background image

Your Global Automation Partner

Instructions for Use

IM18-CCM

Cabinet Guard

Summary of Contents for IM18-CCM Series

Page 1: ...Your Global Automation Partner Instructions for Use IM18 CCM Cabinet Guard...

Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Page 3: ...inciple 8 4 4 Functions and operating modes 9 4 4 1 System partitions and recovery system 9 5 Installing 10 6 Connection 11 6 1 Connecting the device to the higher level via Ethernet 11 6 2 Connecting...

Page 4: ...0 F 49 208 4952 264 more turck com www turck com 11 2 Transferring the firmware update via WinSCP 24 11 3 Carrying out a firmware update with PuTTY 28 12 Repair 30 12 1 Returning devices 30 13 Decommi...

Page 5: ...dangerous situation with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoid...

Page 6: ...electromagnetic compatibility n 2011 65 EU RoHS Directive 2 4 Manufacturer and service Hans Turck GmbH Co KG Witzlebenstra e 7 45472 M lheim an der Ruhr Germany Turck supports you with your projects...

Page 7: ...y only be used as described in these instructions Any other use is not in accordance with the intended use Turck accepts no liability for any resulting damage 3 2 Obvious misuse n The device is not a...

Page 8: ...Pwr Com Err IM18 CCM 10 11 12 7 8 9 4 5 6 1 2 3 Power Fault Communication 37 5 1 48 125 7 4 95 110 4 33 17 5 0 69 120 7 4 75 Fig 1 Front view Fig 2 Dimensions 4 1 1 Indication elements The device is p...

Page 9: ...m provided on the device is the Debian Linux distribution This enables the smart preprocessing of data through the integration of tailored programs The device functions can be programmed as required 4...

Page 10: ...esive foil supplied with the device The device can be mounted on a DIN rail according to EN 60715 TH35 The minimum clearance from other devices must be at least 15 mm RS485 CAN ETH0 Pwr Com Err IM18 C...

Page 11: ...erface is implemented as an RJ45 socket The maximum cable length is 30 m Connect the external sensor to the device via the CAN RS485 interface 87654321 v 1 CAN_H 2 CAN_L 3 4 A RS485 5 B RS485 6 7 8 Fi...

Page 12: ...9 208 4952 0 F 49 208 4952 264 more turck com www turck com 6 4 Wiring diagram 20 30 VDC 2 3 RH C mm 20 30 VDC 5 W ETH0 RS485 CAN Err Com Pwr RD GN GN Fig 7 IM18 CCM wiring diagram 6 5 Terminal assign...

Page 13: ...ice via the console The IP address depends on the selected connection The user sshu also has the possibility to use sudo options Command example This_is_a_console command example path Example output E...

Page 14: ...GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Click the device Click Change or press F2 Set the IP address as well as the network mask if necessary Accept the changes by cl...

Page 15: ...g PuTTY WinSCP or similar NOTICE Insufficiently secured devices Unauthorized access to sensitive data Change the password after the first login Turck recommends the use of a secure password Establish...

Page 16: ...Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com After the login the folder home in the working directory becomes active with restricted write access rights The write and read ope...

Page 17: ...stem partition var 256 MB Variable and temporary data of the system opt 128 MB User programs if necessary user data home 416 MB home folder for all users home temp 32 MB Subfolder in the home director...

Page 18: ...hum Measurement and display of the ambient air humidity all Measurement and display of temperature and air humidity help Display help text Distance sensor distance_ calibrate sh values Calibration of...

Page 19: ...nication active Err Red Error indication 8 1 1 Programming LED indication The LEDs can be programmed as required via the operating system The following table shows the system names and examples for us...

Page 20: ...F 49 208 4952 264 more turck com www turck com 8 2 Querying active system partition The current status of the available systems and the active system can be queried via the follow ing console command...

Page 21: ...V1 00 2020 03 21 9 Setting and parameterization The Linux operating system enables the device functions to be parameterized for the specific application...

Page 22: ...damaged or an update fails the partitions make it possible to revert to the pre vious executable system or recovery system The active system is marked as faulty after three failed boot operations in...

Page 23: ...a suitable tool e g WinSCP or FileZilla or as a secure copy Load the update file e g IM18 CCM30 MTI 24VDC_V1 0 2 raucb via a suitable tool e g WinSCP to the device Alternatively Transfer the update fi...

Page 24: ...e WinSCP and PuTTY tools Requirements n WinSCP is installed n PuTTY is installed n The update file is available as a raucb file on a local computer Transferring a firmware file with WinSCP Log into th...

Page 25: ...V1 00 2020 03 25 Navigate in WinSCP to the memory location of the update file on the host PC Fig 17 WinSCP Memory location of the firmware file on the host PC...

Page 26: ...g the firmware update via WinSCP 26 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com Navigate to the directory home update on the device Fig 18 WinSCP Directory hom...

Page 27: ...directory home update by drag and drop or by clicking Upload Fig 19 Directory home update Confirm with OK a The transfer of the update file is displayed by WinSCP as follows Fig 20 WinSCP File transf...

Page 28: ...ements n PuTTY is installed n The update file was loaded onto the device as a raucb file NOTE The session can be loaded via Load for later repetitions Open PuTTY Enter the following settings in PuTTY...

Page 29: ..._V1 0 2 raucb Fig 22 PuTTY Starting the firmware update Wait until the message Installing Path To Your File file raucb succeeded is displayed Restart the device with the command sudo reboot Fig 23 PuT...

Page 30: ...n equipped with a Decontamination declaration enclosed The decontamination declaration can be downloaded from https www turck de en retoure service 6079 php and must be completely filled in and affixe...

Page 31: ...rature 0 70 C Storage temperature 25 75 C Relative humidity 10 90 internal No condensation at 45 C storage Installation height 2000 m above sea level Type of protection IP20 Housing material Polycarbo...

Page 32: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100016098 2020 03 100016098...