Function description
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
36
5.4
The principle of the data storage mechanism
5.4.1
General
Data storage enables a user to change an IO-Link device when maintenance is required without any
configuration or parameterization.
The IO-Link master, as well as the IO-link device, store the device parameters. The data storage
mechanism serves for synchronizing these different data storage buffers.
In case of a device change, the master writes the stored device parameters to the new device. The
application can be re-started without any further intervention using a configuration tool or similar.
In the BL20/BL67 IO-Link masters, the data storage mode can be set using the parameter "data stor-
age mode" (see
Parameters (Seite 20)
).
Data storage mode
00 = activated (s.
S. 37
)
01 = overwrite (s.
S. 38
)
10 = read in (s.
S. 39
)
11 = deactivated, clear (s.
S. 39
)
A change of parameters in the device is indicated by the status of the DS_UPLOAD_FLAG bit:
DS_UPLOAD_FLAG:
0 = no changes in the device's parameter set
1 = changes in the device's parameter set (e. g. via DTM, at the device, etc.)
Para. IOLD = parameter data of the IO-Link device
Fig. 4: General principle of the data storage mechanism
IO-Link-Master
(IOLM)
IO-Link-Device
(IOLD)
DS_UPLOAD_FLAG
Summary of Contents for BL20-E-4IOL
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 6: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 4...
Page 73: ...71 2018 10 Activate the read access via a rising edge at REQ Fig 25 Activating the read access...
Page 91: ...30 subsidiaries and over 60 representations worldwide www turck com D301333 2018 10 D301333...