Operating
Diagnostic data
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 26
9.4
Diagnostic data
Group diagnostics: undervoltage V1/V2 and overcurrent sensor supply – 0x50 (80),
sub index 0
The group diagnosis indicates errors in the module and sensor supply:
n
Group diagnostics: Diagnostics pending at the module
n
Undervoltage V1 (per module)
n
Undervoltage V2 (per module)
n
Undervoltage V
IOL
(per module)
n
Overcurrent sensor supply (per connector)
Format
Length
Array of bytes
2 byte
0 = no diagnostics
1 = diagnostic message available
Byte 0
Bit offset
15
14
13
12
11
10
9
8
Group
diagnostics
-
-
Undervoltage
supply V2
Undervoltage
supply V1
Undervoltage
supply V
IOL
-
-
Byte 1
Bit offset
7
6
5
4
3
2
1
0
Overcur-
rent VAUX
C7
Overcur-
rent VAUX
C6
Overcur-
rent VAUX
C5
Overcur-
rent VAUX
C4
Overcur-
rent VAUX
C3
Overcur-
rent VAUX
C2
Overcur-
rent VAUX
C1
Overcur-
rent VAUX
C0