Special Manual Operating Mode 

In the basic set up men, first menu item, select Special mode, enter the pulse 

time and pause time. Open the advanced set up menu, second menu item, enter 
the number of complete cycles and pause time between these cycles for the 
connected solenoid valves. 

With this mode, unlike manual mode, the device only runs the solenoid valves for 

the set number of cycles and will remain in stand-by until an operator presses 

S

 

(start / stop) in the main menu to repeat the cycles. This mode is especially 
suited for small filters or filters where the dP has low values or the inverter 
keeps pressure constant and it is hard to work with automatic and proportional 
modes. 

Other Function Descriptions 

Alarms 

This function allows an alarm device to be connected. The alarm device can be 

connected to two alarm relays (see wiring diagram) which are opened when the 
threshold set in the ALARMS menu is exceeded. For details, see the third menu 
item and the description in the Accessing the Alarm menu section. 

When an alarm is triggered, it is signaled on the display by a blinking row that is 

normally occupied by the operating mode. The menu key is used for Reset and 

keys  

  can be used to scroll any alarm items that may have triggered for 

relay no. 1: dP minimum (

if enabled in the menu

), dP Dirty Filter, Replace Filters 

(if enabled in the menu) while failed valve activation is signaled with relay no. 2. 

 

 

Rel ay 1 

Termi nals 8-9  Conn.  P4 

Rel ay 2 

Termi nals 6-7  Conn.  P4 

Rel ay 3 

Termi nals 4-5  Conn.  P4 

 

dP Minimum 

if enabled in the menu 

Valve Activation Failed 

Triboelectric Probe 

Pre - Alarm 

dP Dirty Filter 

 

Triboelectric Probe 

Alarm 

Replace Filters 

if enabled in the menu 

 

Triboelectric Probe 

Peak 

 

 

 

 

 

 

 

 

Summary of Contents for E8T

Page 1: ...hannels I n Mn EE8 T en Rev 00 TURBO Srl Du s t F i l t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 1 Ec...

Page 2: ...be ____________________________________________________________17 Operation Description_________________________________________________________ 18 Manual Operating Mode ______________________________...

Page 3: ...or the control of industrial dust collector system pneumatic cleaning Differential pressure digital control through internal transducer which allows the accurate analysis of the cleaning filter cloggi...

Page 4: ...Proportionate To Dp Value For Remote Pressure Reading from 4 to 20mA x 1 Power Consumption 28 Watts Maximum Load Alarm Relays 3 Normally Closed Display Graphic LCD Backlit Monochromatic B W 128 x 64...

Page 5: ...ectable values for any application Cleaning function with fan off post cleaning by dP fan threshold in automatic proportional mode and by contact in manual special manual modes with selectable number...

Page 6: ...Srl Du s t F i l t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 I n Mn E E8T Rev 0 0 en Dimensions And M...

Page 7: ...s which could generate network interference or instability The unit electric power supply must be protected by a 230Vac 30mA Residual Current Device RCD and a bipolar 230Vac 10A magnet circuit breaker...

Page 8: ...nut Any use not described in this user instruction manual or incorrect use of the device may cause damage to the device or to the equipment connected to it Furthermore incorrect use or tampering with...

Page 9: ...TURBO Srl Du s t F i l t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 9 Electrical Connections To connec...

Page 10: ...o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 I n Mn E E8T Rev 0 0 en Jumper Configuration Power Input 115 VAC 230 VAC In the 24Vac and 24Vdc versions J3 and J4...

Page 11: ...ovides access to settings it is used as RESET in the event of alarms Keys Increase and decrease the values manually start valves in Test mode used to scroll any alarms The S key starts stops solenoid...

Page 12: ...OK key Use the arrows to select the item to be set Use keys to increase or decrease the value and change the item conditions Press exit to save and exit Set Operation Selectable Parameters Operative M...

Page 13: ...hile cleaning cycles are started with the fan off under it Post Cleaning Cleaning Fan off Number of complete cleans with fan off for the number of connected solenoid valves Pulse Time Valve opening ti...

Page 14: ...s exit to save and exit Set Operation Selectable Parameters dP Dirty Filter Enter the dP threshold to trigger the clogged filter alarm Enabling Minimum dP Minimum dP alarm enabling broken sleeve Low A...

Page 15: ...K key Use the arrows to select the item to be set Use keys to increase or decrease the value and change the item conditions Press exit to save and exit Set Operation Selectable Parameters No Valve ON...

Page 16: ...ters Press OK key Use the arrows to select the item to be set Use keys to increase or decrease the value and change the item conditions Press exit to save and exit Set Operation Selectable Parameters...

Page 17: ...ltiple of 0 5 Sec 300 Threshold Alarm 0 01 mg m 1500 Time Alarm Recognition Multiple of 0 5 Sec 60 Threshold Peak 0 01 mg m 3000 Time Recognition Peak Multiple of 0 5 Sec 10 Reference Emissions 0 01 m...

Page 18: ...ic cleaning only when necessary If the device detects clogging over the dP Start Cleaning threshold cleaning is started If clogging drops under the dP Stop Cleaning threshold cleaning is suspended and...

Page 19: ...s pressure constant and it is hard to work with automatic and proportional modes Other Function Descriptions Alarms This function allows an alarm device to be connected The alarm device can be connect...

Page 20: ...uration between one solenoid valve start and the next during post cleaning Pulse time cleaning pulse duration regardless of the fan on operating time Selecting The Number Of Outputs The number of outp...

Page 21: ...5 7 4 0 9 2 21 4 20mA Out Function This function lets you check pressure readings from remote through 4 20mA transmitter Connect the signal to be sent to the remote device to terminals 10_11 on connec...

Page 22: ...ipes between device and filter are not obstructed or damaged The cleaning cycle is not carried out The economizer is in economy mode and therefore does not start up Adjust the start up pressure thresh...

Page 23: ...hen Fan Is Off 2 Pulse Time V Cleaning Fan Off 200 m sec Pause Time V Cleaning Fan Off 20 sec Start Precoating dP 1 50 kpa Language Italian Maintenance The control unit has no parts that can be replac...

Page 24: ...ill replace any electronic component deemed defective exclusively at our workshop except in the presence of contrary agreements to be authorized by the company Warranty Exclusions The warranty will be...

Page 25: ...The manufacturer s address V i a P o 3 3 3 5 2 0 8 1 1 C e s a n o M a d e r n o I t a l y Declares that the product E c o n o m i z e r Model E 8 T Complies with the following directives Directive 2...

Reviews: