6
List Of Functions
F02:
Solenoid valve activation time.
Possible values:
0.05 seconds – 5.00 seconds step 0.01 seconds.
Default = 0.20 seconds.
F03:
Washing pause time between solenoid valves.
Possible values:
001 seconds – 999 seconds step 1 seconds.
Default = 020 seconds.
F04:
Number of connected outputs.
Possible values:
01 – 16 step 1.
Default = 001.
F05:
Output voltage setting, must agree with jumpers.
Possible values:
24 Vdc, 24 Vac , 115 Vac, 230 Vac.
Default = 115 Vac.
F06:
Manual output activation.
Possible values:
1 – number of outputs set in F04.
Press SET to activate the set output.
F13:
Number of post cleaning cycles after stopping the fan.
Possible values:
01 – 99 step 1.
Default = 00.
F14:
Post cleaning mode pause time (fan off).
Possible values:
001 seconds – 999 seconds step 1 seconds.
Default = 010 seconds.
F15:
Maintenance frequency expressed in tens of hours (e.g.: 1=10h, 10=100h).
Possible values:
001 – 999 step 1.
Default = 100 (=1000h).
F16:
Maintenance deadline alarm enable.
Possible values:
0 (disabled) – 1 (enabled).
Default = 0 (disabled).
F17:
Maintenance hour counter reset.
Possible values:
0 (disabled) – 1 (reset).
Default = 0 (disabled).
Note:
The maintenance hour counter will be reset and the F17
parameter will be set back to 0 by setting F17 to 1.
F24
Exclusion of the valve in short circuit.
If set to 1 the valve shorted is excluded from the cycle.
Settable Values 0 (not excluded) - 1 (excluding)
Default = 0 (not excluded).