Turbo Energy Lithium 48V 2.4 kWh Instruction Manual Download Page 11

 

11 

 

Installation method 2: With simple bracket installation 

 

                                                                  

 

 

 

4.4.3.  Electrical installation 

 

Before  connecting  the  power  cables,  use  multimeter  to  measure  cable 
continuity, short circuit, confirm positive and negative, and accurately mark the 
cable labels. 
 
Measuring methods

 

 

 

Power  cable  check:    select  the  buzzer  mode  of  multimeter  and 
detect  both  ends  of  the  same  color  cable.  If  the  buzzer  calls,  it 
means the cable is in good condition. 

 

Short  circuit  judgment:  choose  multimeter  resistor  file,  probe  the 
same end of positive and negative pole, if the resistor shows infinity, 
means that the cable is available. 

 

After  visual  testing  of  power  line  is  connection,  the  positive  and 
negative poles of the battery shall be connected respectively to 
the positive and negative poles of the opposite terminal. 

 
It is better to add a circuit breaker between the inverter and the battery system. 
The selection of the circuit breaker requires: 
 

1.

 

Place the Lithium Series  48V 
2.4  kWh  and  brackets  as 
shown in the figure and insert 
it  into  the  brackets.  Use  4 
screws  to  fix  the  module  on 
the front bracket. 

2.

 

Install 

another 

pair 

of 

brackets  on  the  first  one, 
fixed  by  buckles  between 
them. 

3.

 

Insert the second one 
Lithium Series 48V 2.4 kWh 
into the brackets and 
repeat for more batteries. 

Summary of Contents for Lithium 48V 2.4 kWh

Page 1: ...https www turbo e com Instruction Manual Lithium Series 48V 2 4 kWh Battery...

Page 2: ...tection 7 4 2 4 Other Protection 7 4 3 DIP switch 7 4 4 Assembly and connection 9 4 4 1 Components list 9 4 4 2 Mechanical instalation 10 4 4 3 Electrical installation 11 4 5 Battery parameter setting...

Page 3: ...50Ah Depth of Discharge DoD 90 Nominal Voltage 48V Voltage operating range 40 5 54V Cycle Life 6000 Physical Weight 22 kg Dimensions 480 x 360 x 90 mm Protection class IP20 Battery type LiFePO4 Operat...

Page 4: ...y can be expanded by incorporating more batteries 4 Operation 4 1 Battery front Item Name Definition 1 Power switch OFF ON must be in the ON state when in use 2 Ground connection point Shell ground co...

Page 5: ...t support CAN RS485 communication factory default CAN communication 10 DRY CONTACT 11 ADD DIP switch Battery Status SOC LED1 LED2 LED3 LED4 ALM RUN Shutdown off off off off off off Standby 75 SOC 100...

Page 6: ...ops charging when total voltage or any battery cell voltage reaches the rated protection value during charging stage When total voltage or all cell back to rated range the protection is over 4 2 2 Cur...

Page 7: ...rom the shutdown state if a short circuit occurs the system starts short circuit protection for 60 seconds Self Shutdown When device connects no external loads and power supply and no external communi...

Page 8: ...DELIOS GROWATT HVM Master Slaves Inverter VOLTRONIC Axpert VMIII Axpert King Growatt SPH SPA Master Slaves Inverter GROWATT SPH SPA Master Slaves Inverter GROWATT SPF HVM Master Slaves 3 If the energ...

Page 9: ...Figure Battery B4850 48V 50Ah 480 360 90mm 1 Power cable positive Red 25mm2 L2050m m 1 Power cable negative Black 25mm2 L2050m m 1 Parallel cable positive Red 25mm2 L215mm 1 Parallel cable negative Bl...

Page 10: ...er Manual LIS 24 User manual 1 1 Place the Lithium Series 48V 2 4 kWh unit on the rack bracket as shown in the figure and push the device into the cabin at the installation position The cabinet struct...

Page 11: ...ole if the resistor shows infinity means that the cable is available After visual testing of power line is connection the positive and negative poles of the battery shall be connected respectively to...

Page 12: ...figure Important Connect the specific communication cable supplied by the provider Connect the communication cable between batteries Negative power cable Positive power cable Positive parallel cable...

Page 13: ...ettings Max Charging Bulk Voltage 53 5V Absorption Voltage 53V Float Voltage 52 5V Shut Down cut off Voltage 47V Shut Down cut off SOC 20 Restart Voltage 49V Max Charge Current 25A battery QTY Max Dis...

Page 14: ...the circuit breaker battery input terminal has a voltage output and is greater than 42V then the battery begun to work normally 4 After confirming that the battery output voltage and polarity are corr...

Page 15: ...r current RED Buzzer start Stop charging and find out the cause of the trouble High temp RED Stop charging Discharge state Over current RED Buzzer start Stop discharging and find out the cause of the...

Page 16: ...lacement or add more modules 4 The battery cannot be fully charged to 100 Charging voltage is too low Adjust charging voltage at 53 5V or 54V 5 The power cable sparks once power on and ALM light RED P...

Page 17: ...y place 9 Never expose the battery to fire or water 6 2 Safety warnings 1 Do not disassemble the batteries The inside of the battery has a protective mechanism and a protective circuit to avoid danger...

Page 18: ...completely It can be harmful to the skin and if you touch the eyes wash and go to the hospital immediately for treatment 6 3 Environmental protection Turbo Energy s batteries comply with EU ROHS regu...