CHEST FROZEN SHOWCASE 

TSD-27CF 

 

 

 

Cause Check 

Point 

Correction 

Compressor 

Check coils 
resistances 

Repair Procedure 

1.

 

Replace compressor if measured resistances differ from given standard 

2.

 

Abnormal noise 

 

Not cooling 

Check thermostat 

setting 

Repair Procedure 

1.

 

Operate unit for 10 minutes with thermostat set at maximum 

 

Insufficient cooling 

Check gasket gap 

Repair Procedure 

1.

 

Check if gap can be resolved by adjustment of door hinges fixing screws. 

2.

 

Defrost if accumulation of frost is more than 10mm. 

 

Malfunction due to 

leaks or clogged 
system 

 

Charged (purge) with 

nitrogen into the 
refrigeration system 

& check for leaks on 

welds or clogs 

Repair Procedure 

1.

 

Check for clog or leak in the cooling system.  

2.

 

Repair or replace the clogged or leak section.  

3.

 

Evacuate and change filter dryer. 

4.

 

Purge with nitrogen to clean and check for leaks 

5.

 

Recharge refrigerant, test run and seal system 

 

 

TROUBLE  INSPECTION  

CAUSES  

REMEDY 

Check electric power 
supply voltage 

Open circuit breaker or 
fuse                                        

Fix or replace 

Open Fuse  

Replace  

No Power 

Check electrical circuit 

Worn out or defective A/C 
cord 

Replace  

Check lamp 

Open 

Replace 

No Light 

 

Check lamps socket 

 
 

Corroded 

 

Replace 

Low Cooling 

Check for thermo setting 

Setting too low  

Set thermostat higher 

Deform or warp door 
gasket. 

Adjust door hinges fixing 
screws  

Check leaks 

Poor weld on joints 

Repair, purge with 
nitrogen  re-charge 
refrigerant and test run. 

 

 

 

 
 

Over storage or load or 
heavy frost accumulation 

 

Reduce or re-arrange 
load or defrost unit 

Defective Cooling 
System 

 

Check Thermostat 

 

Check if compressor runs 
by shortening thermostat  

 

Replace thermostat if 
compressor runs. 

 

 

Check PTC starter 
resistance against given 
value 

 

Open, no resistance or 
differ from given value 

 

Replace PTC starter. 

 

 

Check Overload Protector 

 

Check for continuity 

 

Replace if open. 

 

Check for leaks 

Leaks or poor welds  on 
joints 

Repair, re-weld, purge, 
evacuate and recharge 
refrigerant 

Check Compressor 
resistance against given 
specification 

Defective 

 

Replace, weld, purge, 
check for leaks and re-
charge refrigerant, test run 
and seal system 

 

 

Check Pipe System 

 
 

Clogged Pipe System or 
oil choke 

 

1. Evacuate then Purge 
with nitrogen to remove 
clogs 
2. Repair or replace 
clogged section, evacuate, 
purge, check leak and re-
charge refrigerant. Test 
Run and seal system 

 

Summary of Contents for TSD-27CF

Page 1: ...rect Cool Manual Defrost Tropical Power Source 115VAC 60 Hz Volume 138 Liters 4 9 cu ft Rated Current 2 0 Amp Rated Power Input 135 Watts Power Consumption 1 30 kW h 24h High side Low side pressure 15...

Page 2: ...or Lamp None Fan Motor None Compressor KONOR GQY50AD 135 Watts Compressor Oil 290 ml POE Polyol Ester Synthetic PTC Starter 8115PTH7M4R7MC1 3 8 5 6 Max current 18A 180V Overload Protector 11650X011 si...

Page 3: ...CHEST FROZEN SHOWCASE TSD 27CF ELEC CIRCUIT TSD 27CF COOLING SYSTEM TSD 27CF...

Page 4: ...ermostat 1 208 Thermostat panel 1 209 Red indicator light 1 210 Green indicator light 1 211 Thermostat knob 1 212 Thermostat panelcover 213 Castor 2 4 214 Base support 1 215 Screw ST4 2x16 C H 4 216 C...

Page 5: ...Compressor electric box clip 1 308 PTC starter 1 309 Compressor process tube 1 401 Screw M4x22 2 402 Connector box cover 1 403 Connector box support 1 404 Power cord retainer base 1 405 Power cord 1...

Page 6: ...CHEST FROZEN SHOWCASE TSD 27CF Exploded View of TSD 27CF...

Page 7: ...C Min action current 3 36A 70 Overload Protector Model TSD 27CF Abnormal Open TROUBLE SHOOTING Thermostat Repair Procedure 1 Set Thermo Knob to OFF position pull straightened feeler bulb 2 Remove Ther...

Page 8: ...electrical circuit Worn out or defective A C cord Replace Check lamp Open Replace No Light Check lamps socket Corroded Replace Low Cooling Check for thermo setting Setting too low Set thermostat high...

Page 9: ...rect Cool Manual Defrost Tropical Power Source 115VAC 60 Hz Volume 208 Liters 7 3 cu ft Rated Current 3 0 Amp Rated Power Input 200 Watts Power Consumption 1 80 kW h 24h High side Low side pressure 15...

Page 10: ...or Lamp None Fan Motor None Compressor KONOR GQY70AD 165 Watts Compressor Oil 290 ml POE Polyol Ester Synthetic PTC Starter 8115PTH7M4R7MC1 3 8 5 6 Max current 18A 180V Overload Protector 11650X011 si...

Page 11: ...CHEST FROZEN SHOWCASE TSD 35CF ELEC CIRCUIT TSD 35CF COOLING SYSTEM TSD 35CF...

Page 12: ...indicator light 1 213 Thermostat knob 1 215 Dryer filter 1 216 Dryer filter support 1 217 Cappilary tube 1 218 suction tube 1 219 Base support 1 220 Screw ST4 2x16 C H 4 221 Screw 4 2x16 C H 2 222 Ca...

Page 13: ...tion gasket 4 315 Nut M4 2 316 spring 2 317 Fan motor 1 318 Fan cool condenser 1 401 Screw M4x22 2 402 Connector box cover 1 403 Connector box support 1 404 Power cord retainer base 1 405 Power cord 1...

Page 14: ...CHEST FROZEN SHOWCASE TSD 35CF Exploded View of TSD 35CF...

Page 15: ...TC Min action current 3 36A 70 Overload Protector Model TSD 35CF Abnormal Open TROUBLE SHOOTING Thermostat Repair Procedure 1 Set Thermo Knob to OFF position pull straightened feeler bulb 2 Remove The...

Page 16: ...electrical circuit Worn out or defective A C cord Replace Check lamp Open Replace No Light Check lamps socket Corroded Replace Low Cooling Check for thermo setting Setting too low Set thermostat high...

Page 17: ...t Tropical Power Source 115VAC 60 Hz Volume 298 Liters 10 5 cu ft 318 Liters 11 2 cu ft Rated Current 2 5 Amp Rated Power Input 270 Watts Power Consumption 3 2 kW h 24h 3 5 kW h 24h High side Low side...

Page 18: ...3CH2F Refrigerant Charge gm 215 gm Door Lamp None Fan Motor ZCF 200 100V 125V 60Hz Compressor DONPER EU1121BZ 160 Watts Compressor Oil 290 ml POE Polyol Ester Synthetic PTC Starter QP2 4 7C Overload P...

Page 19: ...CHEST FROZEN SHOWCASE TSD 47CF TSD 60CF ELEC CIRCUIT TSD 47CF TSD 60CF COOLING SYSTEM TSD 47CF TSD 60CF...

Page 20: ...older B 1 208 Side cover holder C 1 209 thermostat 1 210 Thermostat panel 1 211 Red indicator light 1 212 Green indicator light 1 213 Thermostat knob 1 215 Dryer filter 1 216 Dryer filter support 1 21...

Page 21: ...e 1 310 Nut M6 4 311 Spring 4 312 Screw M5x10 2 313 anti vibration gasket cover 4 314 Compressor anti vibration gasket 4 315 Nut M4 2 316 spring 2 317 Fan motor ZCF 200 1 318 Fan cool condenser 1 401...

Page 22: ...CHEST FROZEN SHOWCASE TSD 47CF TSD 60CF Exploded View of TSD 47CF...

Page 23: ...CHEST FROZEN SHOWCASE TSD 47CF TSD 60CF Exploded View of TSD 60CF...

Page 24: ...verload current 27A UTC Min action current 3 36A 70 Overload Protector Model TSD 47CF TSD 60CF Abnormal Open Measure the resistance with a tester Ambient temperature Room temperature 25 c Model CBB60...

Page 25: ...5 Recharge refrigerant test run and seal system TROUBLE INSPECTION CAUSES REMEDY Check electric power supply voltage Open circuit breaker or fuse Fix or replace Open Fuse Replace No Power Check elect...

Page 26: ...CHEST FROZEN SHOWCASE TSD 47CF TSD 60CF oil choke with nitrogen to remove clogs 2 Repair or replace clogged section evacuate purge check leak and re charge refrigerant Test Run and seal system...

Reviews: