Device setup.
Rapid parameter set selection (EZY)
The easy controllers feature the EZY parameter which is used to quickly choose a list of
parameters, with corresponding values, for the control of the refrigeration system.
Table 5. SET 1 (EZY=1) – Low temperature (SET POINT : -10
℉
) Electric defrost
Parameter
Description
Min
Max
Default
St
Set point
-30
30
-10
r1
Minimum set point value
-50
30
-30
r2
Maximum set point value
-30
150
30
c2
Minimum compressor off time
0
100
4
do
Type of defrost
0
4
0
dl
Interval between defrost
0
199
6
dt
End defrost temperature set point
-50
127
65
dP
Maximum defrost duration
1
199
60
d4
Defrost on power-up
0
1
1
dd
Dripping time
0
15
2
F0
Enable evaporator fan control
0
1
0
F2
Stop evaporator fan if compressor stop
0
1
0
F3
Evaporator fan status during defrost
0
1
1
Fd
Post-dripping time
0
15
2
Table 6. SET 2 (EZY=3) – Medium temperature (SET POINT : 38
℉
) Air defrost
Parameter
Description
Min
Max
Default
St
Set point
0
50
38
r1
Minimum set point value
-50
50
0
r2
Maximum set point value
0
150
50
c2
Minimum compressor off time
0
100
4
do
Type of defrost
0
4
2
dl
Interval between defrost
0
199
6
dt
End defrost temperature set point
-50
127
40
dP
Maximum defrost duration
1
199
40
d4
Defrost on power-up
0
1
0
dd
Dripping time
0
15
0
F0
Enable evaporator fan control
0
1
0
F2
Stop evaporator fan if compressor stop
0
1
0
F3
Evaporator fan status during defrost
0
1
0
Fd
Post-dripping time
0
15
0