d. Obsolete wires shall be insulated properly or removed completely.

 

 

e. Ballast is no more connected. You may remove it or leave it in as is. If you remove it, dispose of 

 

 

    properly according to local regulation.

 

6) Replace the inner cover.

 

7) Apply the caution label provided with the product.

 

8) Place the LED 2D lamp in the socket.

 

9) Replace fixture cover.

 

10) Turn power on. 

4-pin lamps:

Note: Check the lamp socket condition. If damaged or corroded, replace it with a new one.

Note: Caution label with the following warning shall be placed onto the fixture in a location where readily visible by the user 

during re-lamping and after installation. 

CAUTION: Risk of Injury or Damage. This luminaire has been modified and can no longer operate a fluorescent 2D lamp or an 

LED 2D lamp which is designed for CCG or ECG ballasts. Only use the replacement LED 2D plug-in lamp type or contact 
manufacturer for more information.

 

1) Turn power off.

 

2) Remove fixture cover.

 

3) Remove fluorescent lamp and dispose of properly.

 

4) Open inner cover of the fixture to access ballast and socket wiring.

 

5) Re-wire the fixture according to the following sketch:

 

 

a. Observe original wiring prepared for fluorescent lamp operation: 

  I) Option A: AC input is connected to the left side of the socket (relative to the indicated 
 

 

   lamp orientation).

 

 

II) Option B: AC input is connected to the right side of the socket (relative to the indicated 

 

 

     lamp orientation).

 

 

b. Remove crossed-through wires. When you cut the wires that were connected to the socket, 

 

 

     it is recommended to cut them as far from the socket as possible and re-use them according to

 

 

     step c. below, if their length allow:

  I) Option A: AC input is connected to the left side of the socket (relative to the indicated 
 

 

   lamp orientation).

GR10q socket

ballast

L

N

starter

~

GR10q socket

ballast

L

N

starter

Lamp orientation is 

such that horizontal 

bar is on the bottom 

like this:

~

GR10q socket

ballast

L

N

starter

~

Lamp orientation is 

such that horizontal 

bar is on the bottom 

like this:

Lamp orientation is 

such that horizontal 

bar is on the bottom 

like this: