10/12/2012 1
GI102
THA-*** – Electrical Data – Three-Phase, 208
Voltage
Compressor
Load
Pump
Desup.
Pump
Source
Pump
Total
Min.
Model
(60 Hz)
RLA
LRA
FLA
FLA
FLA
FLA
Ampac-
Max.
Fuse/
HACR
THA-036 200/230-3 13.5 88
1.8 .15 4.4 19.9 23.2 30
THA-048 200/230-3 17.6 123
1.8 .15 4.4 24.0 28.4 40
THA-060 200/230-3 20.5 155
1.8 .15 4.4 26.9 32.0 50
THA-072 200/230-3 23.2 164
1.8 .15 4.4 29.6 35.4 50
THT-*** – Electrical Data – Three-Phase, 208
Voltage
Compressor
Load
Pump
Desup.
Pump
Source
Pump
Total
Min.
Model
(60 Hz)
RLA
LRA
FLA
FLA
FLA
FLA
Ampac.
Max.
Fuse/
HACR
THT-096
200/230-3
17.6 x 2
123 x 2
1.8
.15
4.4
24.0 x 2
28.4 x 2
40 x 2
THT-120
200/230-3
20.5 x 2
155 x 2
1.8
.15
4.4
26.9 x 2
32.0 x 2
50 x 2
THT-144
200/230-3
23.2 x 2
164 x 2
1.8
.15
4.4
29.6 x 2
35.4 x 2
50 x 2
THA-*** – Electrical Data – Three-Phase, 480
Voltage
Compressor
Load
Pump
Desup.
Pump
Source
Pump
Total
Min.
Model
(60 Hz)
RLA
LRA
FLA
FLA
FLA
FLA
Ampac.
Max.
Fuse/
HACR
THA-036
THA-048
THA-060
THA-072
THT-*** – Electrical Data – Three-Phase, 480
Voltage
Compressor
Load
Pump
Desup.
Pump
Source
Pump
Total
Min.
Model
(60 Hz)
RLA
LRA
FLA
FLA
FLA
FLA
Ampac.
Max.
Fuse/
HACR
THT-096
THT-120
THT-144
460/480
15 x 2
75 x 2
20 x 2
Notes:
1.
Dual compressor models contain dual power circuits for the compressors, amperages shown are for each
circuit.
2.
All 3-phase models have 120V service source for internal control transformer and outputs for pumps.
Thus the only current/power from the 3-phase source is the compressor.