Step 5: Connect the DC cable

   

Separate the DC connector.   

 

Connect the DC cable. 

 

 

Tips:

 Use AWG 12 (or 4 mm

2

) cable for DC cable. 

 
Assemble the DC connector.   

 

Plug the connectors into the DC sockets of rapid 
shutdown control unit. 
 

Step 6: Connect the FB1&FB2 port (Optional)

 

Use the 2-port connecter to connect the FB1&FB2 
port to any remote status display device (such as 
indicator lights). When the switch is turned on, the 
FB1&FB2 will be connected. When the switch is 
turned off, the FB1&FB2 will be disconnected.   
 

 

 

Step 7: Start the rapid shutdown control unit

 

Turn the switch of rapid shutdown control unit to 
“ON” position. The rapid shutdown control unit will 
start to work and the status LED will be solid red.   

 