With this Schiltknecht anemometer you have acquired a precision instrument of 
exceptional quality. You also obtain the benefit of our many years’ experience in 
metrology and our close collaboration with Swiss and foreign universities, technical 
colleges and research institutes. 
Our factory employs the greatest care in the manufacture of the MiniAir60. All probes 
have been calibrated in our accredited wind tunnels and are checked to conform to the 
required tolerances. 

A. Description  

The MiniAir60 ist particularly suitable for the heating, air conditioning and ventilation 
engineer. The following characteristics, based on practical requirements and unique in 
their combination, ensure efficient and reliable measurements: 

-

  The aerodynamically optimised probe form represents the basis for accurate 

measurement. The probes are very largely unaffected by flow direction and are 
extremely reliable.  

-

  The interchangeability of the snap heads ensures that there is no interruption of the 

measurement in case of damage. The changeover is extremely easy: the head is 
simply pulled vertically of the instrument. 

 

B. Operating principle 

Measurement sensor 

The impeller speed corresponding to the flow velocity is recorded electronically without 
feedback and converted via transducer. 

General handling tips 

-  Do not bend connection cable (danger of cable break) 
-  Cleaning only according to cleaning instructions 
-  Allow heated high temperature sensors to cool slowly; never cool down with cold water 

or similar. 

-  Remove used batteries immediately and dispose of them properly to prevent leakage 

and damage to the unit. 

-  Strong electromagnetic interference sources (transformers, radios, transmitters, etc.) 

can influence the measurement accuracy. 

 

C. Operation 

 

Connection diagram (3-wire system) 

The cable shield must be connected to the housing shield of the connected device 
(ground the sensor on one side only).  
For unshielded devices, the cable shield must be connected to the device ground (GND) 
(do not ground the sensor). 

ATTENTION 

Wrong connection will destruct the probe (no Pol-Protection) ! 

Response time 

The output signal is instantaneous. 
Response time of the electronics: 
when connecting the power supply (on/off): 

immediately 

Time to reach 63 % of final value: 

 

5.2 ms 

 

Response time of the impellers: 
Increase in flow: 

 

 

1.0 sec. 

Decrease in flow: 

 

 

8.0 sec. 

 

Cleaning instructions flow sensor 

Important: Device and sensor must be switched off or disconnected before cleaning. 
The probes are extremely sensitive measuring instruments and cleaning must therefore 
be carried out with extreme caution. 
Fibres or other foreign objects can be carefully removed with fine tweezers. 
Care must be taken not to bend or otherwise damage the wing or axle. 
Under no circumstances may the adjustment of the bearing screws be changed; incorrect 
measurements may result.  

Never reach into running impellers with hard objects!! 

Never use cleaning agents for plastic sensors that remove the plasticizer from the plastic 
(practically all solvents). 
 
We recommend cleaning the sensors: 

-

  unning water 

-

  soapy water 

-

  pure petrol 

 

Cleaning example: 

1. Carefully swivel the impeller head part in clean pure petrol for approx. 10 minutes. 

Then swivel the impeller head part in clean petrol for approx. 1 minute so that the 
impeller bearings are relubricated. 

If soapy water is used as cleaning solution, it is advisable to thoroughly wash out the 
soap solution with distilled water before lubricating with petrol. 
2. After cleaning, rub the outside of the sensor dry with a clean, lint-free cloth. 
3. Allow the impeller head to dry for approx. 30 minutes. 

 

Only clean the impeller head part! 

Never immerse the sensors completely in the solution. 

 

D. Technical data 

 

Probe 

Medium 

non-corrosive gases 

Measuring ranges:  Flow 

Output 

Accuracies 

 

Micro: 

0.6  bis  20 m/s 

– 2926.7 Hz 

+ 1.0% fs., plus + 3.0% rdg 

 

0.7  bis  40 m/s 

– 2803.8 Hz 

+ 1.0% fs., plus + 3.0% rdg. 

 

Micro Water 

0.04 bis   5 m/s 

–   760.0 Hz 

+ 2.0% fs., plus + 3.5% rdg. 

 

0.05 bis 10 m/s 

–   756.0 Hz 

+ 2.0% fs., plus + 3.5% rdg. 

 

Mini: 

0.4  bis  20 m/s 

– 1804.0 Hz 

+ 1.0% fs., plus + 1.5% rdg. 

 

0.5  bis  40 m/s 

– 1725.0 Hz 

+ 1.0% fs., plus + 1.5% rdg. 

 

Mini Water 

0.02 bis   5 m/s 

–   461.0 Hz 

+ 2.0% fs., plus + 3.0% rdg. 

 

0.03 bis 10 m/s 

–   457.0 Hz 

+ 2.0% fs., plus + 3.0% rdg. 

 

Macro: 

0.2  bis  20 m/s 

– 960.20 Hz 

+ 1.0% fs., plus + 1.5% rdg. 

 

0.3  bis  40 m/s 

– 926.99 Hz 

+ 1.0% fs., plus + 1.5% rdg. 

 

Head diam. 

Micro  

ø 11 x 15 mm 

 

Mini  

ø 22 x 28 mm 

 

Macro 

ø 80 x 85 mm 

 

Access opening 

Micro  

16 mm 

 

Mini  

35 mm 

 

Macro 

120 mm 

 

Probe length 

Micro 

165 mm 

 

Mini 

175 mm 

 

Macro 

225 mm 

 

Cable length 

5 m 

Operating temperature 

-10 bis +80 °C 

(Water: 0 bis +70 °C) 

Storage temperature 

-30 to +100 °C 

 

External power supply 

4.5 

– 5.5 VDC 

Current consumption 

0.5 mA at 5 Volt 

 

Important Informations: 

-

  Avoid moisture, extreme temperatures, vibrations and mechanical shocks. Do not 

shake! 

-

  Cleaned the casing and glass with a soft, slightly damp cloth. Do not use cleaning 

materials or solvents! Do not immerse the system in water! 

-

  Remove exhausted battery immediately or else they may leak and damage the 

instrument. Do your part of the environement! Old batteries don’t belong in the bin, 
take them to a collection point for old batteries or hazardous waste.  

-

  Strong electromagnetical interferences (e.g. transformer, handy, radio transmitter) may 

affect the accuracy of the measuring instrument. 

-

  The system may not be modified! Use only original accessories. 

-

   The product must not have public trash collection or garbage cans be 

disposed of. It must be either according to the WEEE Directive or can be 
disposed of properly to the company Schiltknecht Messtechnik AG are sent 
back at his own expense. 
 

 

Guarantee 

Our guarantee covers verifiable material or manufacturing defects on systems and 
devices for a period of 12 months from delivery. For manhandling the guarantee is not 
applicable. 
In the case of an event bringing the guarantee into operation, the defective part is 
repaired or replaced according to our choice. Transport and travel costs are paid by the 
ordering party. 
The guarantee provisions of the supplier are applicable for non-Schiltknecht material. 
We accept no liability with respect to the suitability of the delivered products for the 
envisaged application. 
Our guarantee is in all cases limited to the defective device. Liability for any secondary 
damages whatever is expressly ruled out. 

 

EC-Declaration of Conformity: 

Instrument:  

Vane anemometer 

Instrument type:  

MiniAir60 

Type designation:  

f.6xx.60.xx 

 

The signing legal authorities state, that the above mentioned equipment meets the 
requirement of the electromagnetic compatibility (EMC) according to the Guideline of 
Counsel 2014/30EU. 

 

The evaluation procedure of conformity was assured according to the following 
standards: 
- EN 55022:2011-12 VDE 0878-22:2011-12 (emission)  
- EN 61000-6-1:2007-10; VDE 0839-6-1:2007-10 (immunity) 
- (With frequencies around 1 MHz it can lead to interference) 
 
Manufacturer:  
TSR Messtechnik AG 
Ebnatstrasse 164 
CH-8207 Schaffhausen Switzerland 
 
Certified according to 

EN ISO 9001:2015

 and 

EN ISO/IEC 17025:2017

 (for air flow) 

 

Date: 30.09.2019 

 

Supply 

Signal 

Ground 

Shield 

yellow 

white 

black 

yellow 

white 

black 

Shield 

WARNING! 

means that death, serious injury or 
significant property damage can 
occur if the appropriate 
precautions are not taken.

 