mduOutputVA OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Output apparent power"
::= { mduOutputEntry 8 }
mduOutputWatts OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Output real power"
::= { mduOutputEntry 9 }
mduOutputCal OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Output current measure calibration data"
::= { mduOutputEntry 10 }
-- End of table
mduPowerStatus OBJECT-TYPE
SYNTAX INTEGER
{
totalLoss(1),
input1OK(2),
input2OK(3),
allOk(4)
-- note: a single input MDU would report allOk
if power is present
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Status of MDU power inlets"
::= { mdu12 5 }
mduVoltageCal OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Voltage measure calibration data"
::= { mdu12 6 }
mduVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Voltage measurement"
::= { mdu12 7 }
mduVoltageFloor OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION