TSI Power Corporation April, 2021 SG03502
ATS-800 Series
Rev. 3
Page
3
of
5
CAUTION: The unit must be placed in a well – ventilated area to prevent risk of fire due to over-
heating. Ventilation slots must not be obstructed.
WARNING: The ATS-800 is not ordinarily intended for use in a stacked configuration with other
ATS-800 units, though this can be done with care. In the event a stacked installation is planned,
please contact TSI Power for assistance.
CAUTION: The ATS must be protected by an upstream branch circuit protector, for both the Pri-
mary and the Backup, at 125% of the ATS current rating (the maximum input current rating as shown
on the ATS product label) per the National Electric Code or per local electrical codes if outside of the
United States.
JP13 (ATS ENABLE)
(Figure 1)
PZ00120-5 Control Board
JP1 (HIGH) or JP2 (LOW)
PZ00127-5 Control Board