TSi Power ATS-00-500x Operating Manual Download Page 28

 

                                                        

TSi Power Corporation                                                                           MC80043,4,5,6,7,8,9,50            
ATS-800 Series Automatic Transfer Switches                                                Rev. 3, April, 2018                 

 

 

TSi Power Corporation                    Proprietary Information 

28 

 

 

 

 

6.16  MC80048  ATS-800  SERIES  HARDWIRE,  230  V,  MODELS  800-3900,  -5900,  -7900 

AND -9900 

  

 

             

                            

 

 

 

 

 

 

 

TSi Power’s ongoing product improvement process makes specifications subject to change. Other companies product

 

names herein are for identification purposes only and may be trademarks of their respective companies.

SPECIFICATION     

ATS-800-3900

ATS-800-5900

ATS-800-7900

ATS-800-9900

ELECTRICAL

  VA at 230 V   

3450

4600

6900

9200

  

Circuit breaker 

15 A

20 A

30 A

40 A

  Switching technology

Mechanical relays

INPUT

  Voltage / Current / Voltage range

230 V / 15, 20, 30, 40 A (184 - 264 V)

   Frequency range

47 to 63 Hz, Caution: Both sources must use same nominal frequency

   Transfer time

Typically 

½ 

cycle

 (

~8 ms for 60 Hz or  ~9.7 ms for 50 Hz)

AC input and output connections

Hardwire terminals                                                                                                                                        

(standard Hardwired units must be installed by a qualified electrician)

OUTPUT

  Voltage / Current

230 V / 15, 20, 30 or 40A

  Load regulation

1 % from no load to full load

  Power efficiency

99 % or higher

AC distribution

Hardwire terminals                                                                                                                                                                         

(standard Hardwired units must be installed by a qualified electrician)

  LED indicators:

Green: Primary output, Yellow: Backup output, Red: No primary or backup AC

  Audible alarm  

Buzzer beeps when loss of primary or backup AC occurs

  Audible alarm on / off  

Enable / Disable switch

  Alarm contacts

Rear-mounted DB-9 connector sends loss of primary / backup AC

PHYSICAL

  Dimensions: Inches / mm

W: 422 mm / 16.63"  H: 43 mm / 1.7" D: 267 mm / 10.5"  

  Weight: lbs / kg

 3.63 kg / 8 lbs

  Integral 19

" F

ront Rack-Mount  

 Standard                                                                     

ENVIRONMENTAL

  Ambient temperature

  0° to 40

°

 C /  32

°

 to 104

°

 F 

AGENCY APPROVALS

  Safety

EN 60950-1                                                                                                                                                                                                                                                                                       

  EMC

Radiated: EN55022-1  Immunity: EN55024

WARRANTY

  Warranty

Two year limited warranty covers parts and labor

Summary of Contents for ATS-00-500x

Page 1: ...MC80047 Hardwire 208 V 800 3800 5800 7800 and 9800 15 20 30 40 A 220 240 V 800 3000 5000 7000 and 9000 15 20 30 40 A MC80048 Hardwire 230 V 800 3900 5900 7900 and 9900 15 20 30 40 A MC80049 Hardwire...

Page 2: ...12 2 2 ATS Circuit Boards 12 2 3 Input Output Circuit Breakers 16 2 4 Audible Alarm Switch 16 3 INSTALLATION 16 3 1 Site Selection Preparation 16 3 2 Required Tools 17 3 3 Unpacking Inspection 17 3 4...

Page 3: ...tic Transfer Switches Rev 3 April 2018 TSi Power Corporation Proprietary Information 3 5 3 Inventory Recommendations for Customer w Large Numbers of ATS Units 22 6 REFERENCE 23 6 1 Specifications 23 6...

Page 4: ...valent to TSi or its authorized agent accompanied by a written receipt showing the date of purchase and both the model name and serial number of the product Warranty does not cover transportation cost...

Page 5: ...phase power sources which allows them to be used with a number of different sources Customers with special requirements can be offered custom programming to address special use situations The ATS is f...

Page 6: ...nt to make users aware of important operating and safety concerns NOTE Specific models of the ATS Series may be ETL Listed to signify conformance with UL CSA or CE requirements For actual Listings see...

Page 7: ...unit The ATS allows redundant AC power to mission critical equipment using any combination of UPS backup generator or other available autonomous AC power sources Sturdy steel enclosure can be front ra...

Page 8: ...e for servicing 1 6 REAR ACCESS See Figures 4 5 6 7 AND 8 The DB 9 Connector Primary and Backup circuit breakers Hardwire Termination compartments and Plugs and Receptacles are accessed from the rear...

Page 9: ...ary Input AC Output 1 62 REAR VIEW OF MC80043 UNIT WITH HARDWIRE INPUT AND OUTPUT CONNECTIONS COVER See Figure 5 Figure 5 Rear view of ATS 800 6000 Hardwire unit showing DB9 connector Primary and Back...

Page 10: ...our IEC60320 C13 AC Output Receptacles 1 7 COMPONENT LOCATIONS 1 71 TOP VIEW WITH COVER REMOVED See Figure 8 Removing the top cover exposes the main wiring and major components of the ATS Series Befor...

Page 11: ...800 with top cover removed Primary AC Input Compartment Backup 15 A 20 A 30 A or 40 A Circuit Breaker Compartment Cover Mounting Holes Primary 15 A 20 A 30 A or 40 A Circuit Breaker AC Output Compart...

Page 12: ...TS 800 System Architecture 2 2 ATS SERIES CIRCUIT BOARDS 2 21 Main Control Circuit Board Assemblies See Figures 10 and 11 Two main control circuit boards are used in the ATS Series The PZ00120 5 is us...

Page 13: ...roprietary Information 13 Figure 10 PZ00120 5 Main Control Circuit Board Assembly for ATS 800 2000 3000 4000 5000 6000 and 7000 models Circuit Board Mounting Holes for Snap On Standoffs Circuit Board...

Page 14: ...anel of the ATS housing and attached by means of a ribbon cable and connector to the main control board These LEDs as shown in Figure 3 and 12 signify the following Green Primary LED ON indicates Prim...

Page 15: ...ts are outlined in section 4 3 Figure 13 PZ00129 DB 9 Alarm Circuit Board Assembly 2 3 INPUT OUTPUT CIRCUIT BREAKERS See Figure 13 One two pole circuit breaker located in the rear of the unit connects...

Page 16: ...r Figure 14 Primary Backup Type AC Input Two Pole Circuit Breakers 15 20 30 40 A 2 4 AUDIBLE ALARM SWITCH See Figure 15 Figure 15 P N SE00002 Audible Alarm On Off Switch 3 INSTALLATION 3 1 SITE SELECT...

Page 17: ...TION 3 31 The units are shipped in individual cartons and may come stacked on wooden pallets depending on the size of the order In this configuration the units are placed on the pallet with protective...

Page 18: ...narily intended for use in a stacked configuration with other ATS 800 units although this can be done with care In the event a stacked installation is planned please contact TSi Power for assistance 3...

Page 19: ...ed screwdriver terminate the incoming backup wires on the terminal blocks behind the rear cover marked Backup Input These terminals are marked as follows LI for backup input line or L1in for backup in...

Page 20: ...input frequency is within 5 of that specified Both primary and backup must be the same nominal frequency 2 Turn on the Backup AC circuit breaker in the rear of the ATS unit Make sure that the audible...

Page 21: ...Status DB 9 Pins are _5__NO _1__NC__2_COM Backup AC Input Status DB 9 Pins are _6__NO _3__NC _4__COM 4 32 When Primary AC Input is present and IN SPECIFICATION there is an OPEN circuit between pin_5...

Page 22: ...oard assembly for ATS 800 2000 3 4 5 6 or 7000 models Customer must provide voltage amperage Frequency options PZ00127 5 Main Control Board assembly for ATS 800 8000 or 9000 and 9900 models Customer m...

Page 23: ...Hz or 9 7 ms for 50 Hz Input output wire size 14 AWG 2 08 mm 12 AWG 3 3 mm 10 AWG 5 26 mm 8 AWG 8 36 mm AC input and output connections Hardwire terminals standard Hardwired units must be installed b...

Page 24: ...ther configurations available O U TP U T Voltage C urrent 120 V 15 20 A Load regulation 1 from no load to full load P ow er efficiency 99 or higher R eceptacle m odels 2002 2003 2004 R eceptacle m ode...

Page 25: ...e same nominal frequency Transfer time Typically cycle 8 ms for 60 Hz or 9 7 ms for 50 Hz AC input connections IEC60320 C 14 IEC60320 C 20 OUTPUT OUTPUT OUTPUT OUTPUT Voltage Current 230 V 15 20 A Loa...

Page 26: ...2 0 P L6 2 0 P IE C 6 0 3 2 0 C 2 0 O ther co nfig uratio ns availab le O U T P U T V o ltag e C urrent 2 0 8 V 1 5 2 0 A 2 2 0 V 2 4 0 V 1 5 2 0 A Lo ad reg ulatio n 1 fro m no lo ad to full lo ad P...

Page 27: ...m e Typically cycle 8 m s for 60 Hz or 9 7 m s for 50 Hz AC input connections Hardwire term inals standard Hardwired units m ust be installed by a qualified electrician OUTPUT Voltage Current 208 V 15...

Page 28: ...lly cycle 8 ms for 60 Hz or 9 7 ms for 50 Hz AC input and output connections Hardwire terminals standard Hardwired units must be installed by a qualified electrician OUTPUT Voltage Current 230 V 15 20...

Page 29: ...9 7 ms for 50 Hz AC input connections Hardwire terminals standard Hardwired units must be installed by a qualified electrician OUTPUT Voltage Current 208 V 15 20 30 or 40 A 220 or 240 V 15 20 30 or 4...

Page 30: ...cycle 8 ms for 60 Hz or 9 7 ms for 50 Hz AC input connections Hardwire terminals standard Hardwired units must be installed by a qualified electrician OUTPUT Voltage Current 230 V 15 A 230 V 20 A Load...

Page 31: ...015 IEC320 C 13 JP00101 Optional ATS 800 3000 15 220 V 240 V 50 60 Hz Hardwire JP00001 Hardwire JP00001 N A ATS 800 3002 15 220 V 240 V 50 60 Hz 6 15P JP00042 6 15R JP00043 6 WI40302 ATS 800 3003 15 2...

Page 32: ...IEC60320 C 20 JP00100 IEC60320 C 19 JP00121 Optional ATS 800 6000 30 120 V 50 60 Hz Hardwire JP00001 Hardwire JP00001 N A ATS 800 7000 30 220 V 240 V 50 60 Hz Hardwire JP00001 Hardwire JP00001 N A AT...

Reviews: