............ www.truemfg.com ............
True Food Service Equipment, Inc.
6
6
INSTALLATION / OPERATION INSTRUCTIONS
CONDUCTORS AND CIRCUITS
Wire Gauge for 2% Voltage Drop in Supply Circuits.
115 Volt
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100
120
140
160
2
14 14 14 14 14 14 14 14 14 14 14 14
3
14 14 14 14 14 14 14 14 14 14 14 12
4
14 14 14 14 14 14 14 14 14 12 12 12
5
14 14 14 14 14 14 14 12 12 12 10 10
6
14 14 14 14 14 14 12 12 12 10 10 10
7
14 14 14 14 14 12 12 12 10 10 10 8
8
14 14 14 14 12 12 12 10 10 10 8 8
9
14 14 14 12 12 12 10 10 10 8 8 8
10
14 14 14 12 12 10 10 10 10 8 8 8
12
14 14 12 12 10 10 10 8 8 8 8 6
14
14 14 12 10 10 10 8 8 8 6 6 6
16
14 12 12 10 10 8 8 8 8 6 6 6
18 14
12
10
10 8 8 8 8 8 8 8 5
20 14
12
10
10 8 8 8 6 6 6 5 5
25 12
10 10 8 8 6 6 6 6 5 4 4
30 12
10 8 8 6 6 6 6 5 4 4 3
35 10
10 8 6 6 6 5 5 4 4 3 2
40 10 8 8 6 6 5 5 4 4 3 2 2
45 10 8 6 6 6 5 4 4 3 3 2 1
50 10 8 6 6 5 4 4 3 3 2 1 1
Wire Gauge for 2% Voltage Drop in Supply Circuits.
230 Volt
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100
120
140
160
5
14 14 14 14 14 14 14 14 14 14 14 14
6
14 14 14 14 14 14 14 14 14 14 14 12
7
14 14 14 14 14 14 14 14 14 14 12 12
8
14 14 14 14 14 14 14 14 14 12 12 12
9
14 14 14 14 14 14 14 14 12 12 12 10
10 14 14 14 14 14 14 14 12 12 12 10 10
12 14 14 14 14 14 14 12 12 12 10 10 10
14 14 14 14 14 14 12 12 12 10 10 10 8
16 14 14 14 14 12 12 12 10 10 10 8 8
18 14 14 14 12 12 12 10 10 10 8 8 8
20 14 14 14 12 10 10 10 10 10 8 8 8
25 14 14 12 12 10 10 10 10 8 8 6 6
30 14 12 12 10 10 10 8 8 8 6 6 6
35 14 12
10 10 10 8 8 8 8 6 6 5
40 14 12
10 10 8 8 8 6 6 6 5 5
50 12 10
10 8 6 6 6 6 6 5 4 4
60 12 10 8 6 6 6 6 6 5 4 4 3
70 10 10 8 6 6 6 5 5 4 4 2 2
80 10 8 8 6 6 5 5 4 4 3 2 2
90 10 8 6 6 5 5 4 4 3 3 1 1
100 10 8 6 6 5 4 4 3 3 2 1 1