6.1.3 Settings examples
Example 1: TVR/200/Easy
Nominal volume flow rate, V
nom
, of the control unit - 1459 m³/h
Desired volume flow rate control range
- V
min
: 400 m³/h to V
max
: 1000 m³/h
Billing solution:
V
min
: 400 m³/h / 1459 m³/h
×
100
≈
28%
V
max
: 1000 m³/h / 1459 m³/h
×
100
≈
69%
Example 2: TVJ/400 x 200/Easy
Nominal volume flow rate, V
nom
, of the control unit - 2592 m³/h
Desired volume flow rate control range
- V
min
: 650 m³/h to V
max
: 2250 m³/h
Billing solution:
V
min
: 650 m³/h / 2592 m³/h
×
100
≈
25%
V
max
: 2250 m³/h / 2592 m³/h
×
100
≈
87%