3
Structure and functional description
3.1 Product overview types LVC, TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA
Fig. 1: Easy controller mounted on the control unit, i. e. TVR
1
Easy-controller
2
Test hoses
3
VAV terminal unit
4
Sensor tubes of the control unit
5
Wire clamping bracket
6
Scale sticker for setting V
min
/V
max
7
Terminals
8
'Test' push button
9
LED for displaying the operating states, see table
10
V
min
potentiometer
11
V
max
potentiometer
12
Axle mounting (positive connection or clamping
block)
13
Travel stops
14
Protective cap
15
Tube connection transducer
–
Adjustments sticker on VAV terminal unit (not pic-
tured)
Detection of operating states (LED)
LED
Operating status
On
Target volume flow rate reached
Off
Test push button pressed
No supply voltage
Easy controller faults
Flashes (slowly 0.5 Hz)
Actual value
≠
setpoint value, controller tries to control to the setpoint
value
Test operation started
Synchronisation process active
Flashes (rapidly 2.5 Hz)
Direction of rotation change confirmation
direction of rotation’ on page 25
Then slowly flashing until the synchronisation process is completed.
Structure and functional description
Product overview types LVC, TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA
Control component Easy for VAV terminal units
10