Table of the fan rating groups
According to ISO 14694 (2003), Chapter 8.4
Application
Max. drive capacity [kW]
Fan rating group
Building ventilation
≤ 3.7
BV-2
> 3.7
BV-3
Hazardous gases
≤ 37
BV-3
> 37
BV-4
Table of impeller gaps for roof fans
Size
Impeller gap (+ tolerance) in mm
Immersion depth (+ toler-
ance) in mm
DRH, DRV, DRVF, DRVF-
H, BVD
DRVF-H-ex
DRH, DRV, DRVF, DRVF-
H, DRVF-H-ex, BVD
Minivent 1
5.0 (+1.0)
3.0 (+1.0)
Minivent 2
5.0 (+1.0)
3.0 (+1.0)
Minivent 3
5.0 (+1.0)
3.0 (+1.0)
Minivent 6
5.0 (+1.0)
3.0 (+1.0)
250
3.0 (+1.0)
4.0 (+1.5)
3.0 (+1.0)
280
3.0 (+1.0)
3.0 (+1.0)
315
3.0 (+1.0)
5.5 (+2.0)
3.0 (+1.0)
355
3.5 (+1.5)
5.0 (+2.0)
8.0 (+1.5)
400
4.0 (+1.5)
5.0 (+2.0)
9.0 (+1.5)
450
4.0 (+1.5)
9.0 (+1.5)
500
5.0 (+2.0)
5.5 (+2.0)
12.0 (+2.0)
560
5.0 (+2.0)
12.0 (+2.0)
630
6.0 (+2.5)
9.5 (+2.5)
12.0 (+2.5)
710
6.0 (+2.5)
7.0 (+2.5)
11.0 (+2.5)
Tables
Centrifugal roof fans DRH; DRV; DRVF; DRVF-H; BVD; BVD(F600)
54