The arrangement of the AHU casing units is given in
the order-specific approval drawing.
Fig. 11: Unit arrangement with anti vibration elements
1.
Position the slide plates ( Fig. 11 /3, by others)
under the base frames ( Fig. 11 /2) of the AHU
casing units ( Fig. 11 /1).
2.
Move the AHU casing units as close together as
possible.
Fig. 12: Aligning AHU casing units
3.
Align the AHU casing units so that they are flush
with one another ( Fig. 12 /1).
Setting up units with a base frame
Fig. 13: Attaching a ratchet strap
1.
Attach a ratchet strap to the base frames of two
AHU casing units ( Fig. 13 ).
2.
Tighten the ratchet strap.
ð
The AHU casing units come closer together as
you tighten the strap around the base frames.
Alternatively:
Setting up units without a base frame
1.
Attach a ratchet strap to the bottom or top areas of
two AHU casing units.
2.
Tighten the ratchet strap.
ð
The AHU casing units come closer together as
you tighten the strap.
4.4.2 Assembling AHU casing units
Before assembly
Remove all transport tubes and transport protection
devices from the AHU casing units.
Have all the required tools ready.
Have all the applicable documents at hand.
Remove all separately supplied materials and
accessories from the AHU casing units.
Compressed seals will recover fully to their original
state about 60 minutes after the transport protection
devices have been removed.
Setup and assembly
Setting up and assembling the air handling unit > Assembling AHU casing units
Air handling unit X-CUBE Ex
26