– View / modify setpoints and Schedule

Upper return temperature

If the return temperature reading rises over 

this setpoint value, the AHU will try to cool down the supply air.

Lower return temperature

If the return temperature reading lowers under 

this setpoint value, the AHU will try to heat up the supply air.

Lower return temperature. 

When the AHU is cooling, it will not supply 

air cooler than this temperature setpoint.

Upper supply temperature. 

When the AHU is heating, it will not supply 

air warmer than this temperature setpoint.

Return humidity

Return humidity value that is intended to be reached by 

the humidifier.

Maximum supply humidity

. When the AHU is humidifying, it will not 

exceed this value in the supply air.

Airflow setpoints

Depending on the AHU’s configuration, they will be 

showed in flow units [l/s] or pressure units [Pa]
Supply and return have independent setpoints.

Time switch program

Here the schedule is set up by the user when 

there is no external BMS or when needed.
Initially, the Monday start/stop timing is set and afterwards it can be 
copied on the rest of the required weekdays.

Start time

Stop time

Copy schedules 

from Monday

– Date / time adjust

All rights reserved  © TROX ESPAÑA, S.A.

– Alarms

Red Alarm

Button

Active Alarm

Press the 

button

When the 

malfunction has 

been resolved

Press the 

button

Acknowledge and execute

Date and time when it has 
been produced

Alarm button 

not lighted

Alarm 

deactivated

Alarm 

Description

Alarm priority

Critical A: stops the unit

Low B: does not stop the unit

S/QGTKMCONTROL/EN/1