Thermokon, without selector switch, Berker S.1
X9
1
2
3
4
5
7
5
4
3
2
1
8
1
2
9
10
6
Fig. 20: Wiring of Thermokon control panel to terminal
X9
1
Control panel without selector switch, for flush
mounting, suitable for switch programme Berker
S.1, type WRF07 PTD NTC 20k BType6 5k gn,
TROX order no. A00000079778
2
LiYCY 5 x 0.5 mm² shielded (by others)
Thermokon, without selector switch, Busch Jäger
Futura
X9
1
2
3
4
5
7
5
4
3
2
1
8
1
2
9
10
6
Fig. 21: Wiring of Thermokon control panel to terminal
X9
1
Control panel without selector switch, for flush
mounting, suitable for switch programme Busch
Jäger Futura, type WRF07 PTD NTC 20k BType6
5k gn, TROX order no. A00000079779
2
LiYCY 5 x 0.5 mm² shielded (by others)
4.6 Connection of external inputs and
outputs
External switch inputs
X3
6
5
4
3
2
X4
+ 24 VDC
+ 24 VDC
+ 24 VDC
+ 24 VDC
+ 24 VDC
+ 24 VDC
1
1
Fig. 22: Wiring example of window contact
1
Connecting cable LiYCY 2 x 0.5 mm² (by others)
Terminal connections X3
No.
Function
Switch
Open
Closed
1
Fume cupboard
switch
Inactive
Active
2
Changeover
1
Heating
Cooling
3
Operating
enable
Off
Automatic
4
Fire emergency
stop
1
Off
Automatic
5
Window con-
tact
1
Off
Automatic
6
PIR sensor
Valid oper-
ating mode
Occupied
1 cable break safety device
Installation
Connection of external inputs and outputs > Installing the ventilation unit
Decentralised ventilation units Under sill units
24