Accessories 2
Flexible connector
06/2015
FK-EU
– DE/en
1
Application
– For information on how to limit such loads
please refer to the guideline regarding fire
protection requirements on ventilation systems
(Lüftungsanlagen-Richtlinie, LüAR)
– As ducts may expand and walls may become
deformed in the event of a fire, we recommend
using flexible connectors for the following
applications: installation in lightweight partition
walls, in lightweight shaft walls,
with fire batts, and in lightweight fire walls
– Flexible connectors should be installed
in such a way that both ends can compensate
both tension and compression
– Flexible ducts can be used as an alternative
– For certain heights an extension piece
may be required, see table
– The fixing holes in the flexible connectors
and extension pieces match those
in the fire damper flanges
– Flexible connectors
are also available separately
Materials and surfaces
– Flexible connectors made of galvanised steel
and fibre-reinforced plastic
– Fire resistance properties to 4102; B2
K 4 – 1.1 – 29
Description
Flexible connector
/
S0
/
/
0S
/
/
SS
/
Order code detail
Technical data
Flexible connector for FK-EU · FK-EU-1 · FK-EU-2 · FK-EU-7
Operating side
Installation side
Order code
Flexible connector –
S0
–
Flexible connector
0S
Flexible connector Flexible connector
SS
Location and length of extension pieces [mm]
H
Operating side
Installation side
L
Order code
200 – 550
–
–
375/500
S0
600 – 800
120
–
375/500
S0
200 – 300
–
–
500
0S
350 – 550
–
120
500
0S
600 – 800
–
260
500
0S
200 – 300
–
–
500
SS
350 – 550
–
120
500
SS
600 – 800
120
260
500
SS
* flexible length
≥
100 mm when installed
The distance »a« between
the open damper blade
and the flexible connector
should be 50 mm.
Flexible connector
~ 160*
~ 185
ݢ
ݣ
ݢ
①
Flexible connector
②
Extension piece